2017-06-07 02:34:131) WRITE THE SIZE OF THE NEW BACKFLOW DEVICE BEING
 INSTALLED ON THE PERMIT APPLICATION AND ALSO INDICATE
 THE SIZE ON THE MANUFACTURER'S SPECIFICATION SHEET.WPB
 AMEND TO FBC SEC. 107.2.1.
 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES.
 THIS IS NOT SPECIFIED ON THE SPECIFICATION SHEET THAT
 HAS BEEN SUBMITTED.
 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED
 IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH
 PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO
 ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE
 DEVICE.
 6) ALL DEVICES SHALL BE LEAD FREE. CIRCLE THE LF UNIT
 ON THE SPECIFICATION SHEET TO ENSURE THERE IS NO
 CONFUSION AS WWHICH DEVICE IS APPROVED.
 NOTE: THE PERMIT CARD AND MANUFACTURER'S SPECIFICATIONS
 SHALL BE ON THE JOBSITE FOR INSPECTION.
  
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL CAN BE FOUND AT :
 HTTP://WPB.ORG/UTILITIES/BACKFLOW
 UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS:
 WWW.USC.EDU/DEPT/FCCCHR