Date |
Text |
2017-06-07 02:34:13 | 1) WRITE THE SIZE OF THE NEW BACKFLOW DEVICE BEING |
| INSTALLED ON THE PERMIT APPLICATION AND ALSO INDICATE |
| THE SIZE ON THE MANUFACTURER'S SPECIFICATION SHEET.WPB |
| AMEND TO FBC SEC. 107.2.1. |
| 2) ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY OF |
| SOUTHERN CALIFORNIA'S ( USC ) LIST OF APPROVED DEVICES. |
| THIS IS NOT SPECIFIED ON THE SPECIFICATION SHEET THAT |
| HAS BEEN SUBMITTED. |
| 4) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO |
| CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE |
| CITY?S REQUIREMENTS. |
| 5) BACKFLOW PREVENTION DEVICES SHALL BE LOCATED |
| IMMEDIATELY AFTER THE METER AND MUST BE TESTED AND |
| CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| DEPARTMENT. PLEASE CONTACT THE CITY OF WEST PALM BEACH |
| PUBLIC UTILITIES CENTRAL OPERATIONS AT 561-822-2210 TO |
| ARRANGE FOR THE UTILITIES DEPARTMENT TO CERTIFY THE |
| DEVICE. |
| 6) ALL DEVICES SHALL BE LEAD FREE. CIRCLE THE LF UNIT |
| ON THE SPECIFICATION SHEET TO ENSURE THERE IS NO |
| CONFUSION AS WWHICH DEVICE IS APPROVED. |
| NOTE: THE PERMIT CARD AND MANUFACTURER'S SPECIFICATIONS |
| SHALL BE ON THE JOBSITE FOR INSPECTION. |
| |
| THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL |
| MANUAL CAN BE FOUND AT : |
| HTTP://WPB.ORG/UTILITIES/BACKFLOW |
| UNIVERSITY OF SOUTHERN CALIFORNIA WEBSITE ADDRESS: |
| WWW.USC.EDU/DEPT/FCCCHR |
| QUESTIONS REGARDING PERMITTING REQUIREMENTS MAY BE |
| DIRECTED TO: |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| CITY OF WEST PALM BEACH |
| 561-805-6692 |
| [email protected] |
| |