Plan Review Notes For Permit 17060200 |
Permit Number |
17060200 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-08-15 14:02:23 | 08/15/17 MET WITH JUNIOR. HE WANTS BUILDING PROVISO TO | | GET PERMIT. REVISION FEES WILL APPLY. | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- REVISE ENERGY CALCULATIONS: A)BUILDER'S NAME. B)AREA | | ON ITEM #6 FOR MASTER SUITE & LEISURE ROOM. C)ITEM #9 | | IS MISSING LEISURE ROOM. ALSO, ADD FRAMED WALL AREA AT | | MASTER SUITE. D)CEILING AREA ON ITEM #10. E)ROOF TYPE | | IS MISSING THE GABLE. F)REVISE WINDOW ORIENTATION & | | SQUARE FOOTAGE TO MATCH PLANS. | | 2- REVISE MASTER BEDROOM EGRESS WINDOW SIZE. | | 3- PROVIDE PRODUCT APPROVAL FOR: A) SWING DOOR. NEED | | FL. PRODUCT APPROVAL COVER PAGE. B) LEISURE RM WINDOWS | | NEED TO HAVE HURRICANE IMPACT PROTECTION. NEED SHUTTERS | | PRODUCT APPROVALS AND INSTALLATION SCHEDULE. | | 4- ARCHITECT TO APPROVE ALL PRODUCT APPROVALS. | | 5- NEED LEISURE RM EXT. DOOR FRAMING DETAIL. SPECIFY | | ALL FRAMING MEMBERS & CONNECTORS. | | 6- NEED COPIES OF ANSI Z97.1 TEST DONE FOR THE 3M | | SAFETY FILM SPECIFIED IN THE LEISURE ROOM WINDOWS. |
|