2017-08-08 10:58:32 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| NO MECHANICAL INFORMATION WAS SUBMITTED FOR THE FIRST |
| REVIEW. THIS IS THE FIRST TIME MECHANICAL INFORMATION |
| IS SUBMITTED. |
| |
| 1- A/C DRAWING SUBMITTED HAS A COPY OF THE ARCHITECT'S |
| SEAL AND SIGNATURE. A/C PLANS NEEDS TO HAVE THE |
| ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT SHOWN ON |
| THE TITLE BLOCK AS REQUIRED BY CHAPTER 481 F.S. WHEN |
| SUBMITTING DRAWINGS FOR PUBLIC RECORDS. |
| |
| 2- THE LEISURE ROOM NEEDS TO COMPLY WITH THE BALANCED |
| RETURN AIR SECTION M1602.4 FBC-RESIDENTIAL. 5TH EDITION |
| (2014). REVISE A/C PLAN AS REQUIRED. |
| |
| 3- IT LOOKS LIKE THE RETURN AIR GRILL SHOWN ON THE |
| LIVING ROOM IS TOO CLOSE TO THE EXISTING FIREPLACE. IT |
| LOOKS LIKE IT'S LESS THAN 10 FEET. THIS IS A PROHIBITED |
| LOCATION. REVISE AS REQUIRED. SEC. M1602.2 |
| FBC-RESIDENTIAL. |
| |
| 4- EQUIPMENT SIZING CALCULATIONS SUBMITTED: |
| A) PLAN FOR A/C SUBMITTED SHOWS THAT AIR IS DISTRIBUTED |
| TO ALL ROOMS, INCLUDING THE LEISURE ROOM. CALCULATIONS |
| SUBMITTED DON'T INCLUDE THIS ROOM. REVISE AS REQUIRED |
| TO MATCH PLAN. SEC. R403.6.1 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| B) CFM'S SHOWN ON THE CALCULATIONS DON'T MATCH CFM |
| SHOWN ON A/C PLAN. REVISE AS REQUIRED TO MATCH. SEC. |
| R403.6.1 FBC-ENERGY CONSERVATION. |
| |
| C) SIZE OF ROOMS AND AREA OF ROOMS DON'T MATCH PLANS. |
| REVISE AS REQUIRE TO MATCH. SEC. R403.6.1 FBC-ENERGY |
| CONSERVATION. |
| |
| D) COORDINATE ALL THE COMPONENTS OF THE HOUSE WITH |
| PLANS. NOT ALL THE WALLS ARE CONCRETE BLOCK WALL. THERE |
| ARE SOME WOOD FRAMED WALLS. ALSO, USE THE SOFTWARE |
| DEFAULT FACTOR FOR GLAZING U-FACTOR AND SHGC FACTOR OR |
| PROVIDE INFORMATION SHOWING THAT THE EXISTING WINDOWS |
| HAVE THE SPECIFIED FACTORS. REVISE AS REQUIRED TO MATCH |
| PLANS. SEC. R403.6.1 FBC-ENERGY CONSERVATION. |
| |
| E) PAGE OF 12 OF CALCULATIONS SUBMITTED SPECIFY NATURAL |
| GAS FURNACE AS THE HEATING SYSTEM. PLANS DON'T SHOW ANY |
| NATURAL GAS FURNACE. REVISE AS REQUIRED TO MATCH PLANS. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD |
| DRAWINGS FOR REVIEW. |
| |