2017-08-08 10:58:32RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 NO MECHANICAL INFORMATION WAS SUBMITTED FOR THE FIRST
 REVIEW. THIS IS THE FIRST TIME MECHANICAL INFORMATION
 IS SUBMITTED.
  
 1- A/C DRAWING SUBMITTED HAS A COPY OF THE ARCHITECT'S
 SEAL AND SIGNATURE. A/C PLANS NEEDS TO HAVE THE
 ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT SHOWN ON
 THE TITLE BLOCK AS REQUIRED BY CHAPTER 481 F.S. WHEN
 SUBMITTING DRAWINGS FOR PUBLIC RECORDS.
  
 2- THE LEISURE ROOM NEEDS TO COMPLY WITH THE BALANCED
 RETURN AIR SECTION M1602.4 FBC-RESIDENTIAL. 5TH EDITION
 (2014). REVISE A/C PLAN AS REQUIRED.
  
 3- IT LOOKS LIKE THE RETURN AIR GRILL SHOWN ON THE
 LIVING ROOM IS TOO CLOSE TO THE EXISTING FIREPLACE. IT
 LOOKS LIKE IT'S LESS THAN 10 FEET. THIS IS A PROHIBITED
 LOCATION. REVISE AS REQUIRED. SEC. M1602.2
 FBC-RESIDENTIAL.
  
 4- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) PLAN FOR A/C SUBMITTED SHOWS THAT AIR IS DISTRIBUTED
 TO ALL ROOMS, INCLUDING THE LEISURE ROOM. CALCULATIONS
 SUBMITTED DON'T INCLUDE THIS ROOM. REVISE AS REQUIRED
 TO MATCH PLAN. SEC. R403.6.1 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 B) CFM'S SHOWN ON THE CALCULATIONS DON'T MATCH CFM
 SHOWN ON A/C PLAN. REVISE AS REQUIRED TO MATCH. SEC.
 R403.6.1 FBC-ENERGY CONSERVATION.
  
 C) SIZE OF ROOMS AND AREA OF ROOMS DON'T MATCH PLANS.
 REVISE AS REQUIRE TO MATCH. SEC. R403.6.1 FBC-ENERGY
 CONSERVATION.
  
 D) COORDINATE ALL THE COMPONENTS OF THE HOUSE WITH
 PLANS. NOT ALL THE WALLS ARE CONCRETE BLOCK WALL. THERE
 ARE SOME WOOD FRAMED WALLS. ALSO, USE THE SOFTWARE
 DEFAULT FACTOR FOR GLAZING U-FACTOR AND SHGC FACTOR OR
 PROVIDE INFORMATION SHOWING THAT THE EXISTING WINDOWS
 HAVE THE SPECIFIED FACTORS. REVISE AS REQUIRED TO MATCH
 PLANS. SEC. R403.6.1 FBC-ENERGY CONSERVATION.
  
 E) PAGE OF 12 OF CALCULATIONS SUBMITTED SPECIFY NATURAL
 GAS FURNACE AS THE HEATING SYSTEM. PLANS DON'T SHOW ANY
 NATURAL GAS FURNACE. REVISE AS REQUIRED TO MATCH PLANS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMIT OLD
 DRAWINGS FOR REVIEW.
  