2017-08-02 14:03:18 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. IN THE RESPONSE LETTER PROVIDED, MR. PORTER ASKED TO |
| BE SUPPLIED WITH THE FBC RESIDENTIAL CODE SECTION THAT |
| REFERENCES BACK TO USING THE NEC CODE SECTIONS CITED. |
| SECTION E3401.1 STATES: "THE PROVISIONS OF CHAPTERS 34 |
| THROUGH 43 SHALL ESTABLISH THE GENERAL SCOPE OF THE |
| ELECTRICAL SYSTEM AND EQUIPMENT REQUIREMENTS OF THIS |
| CODE. CHAPTERS 34 THROUGH 43 COVER THOSE WIRING METHODS |
| AND MATERIALS MOST COMMONLY ENCOUNTERED IN THE |
| CONSTRUCTION OF ONE- AND TWOFAMILY DWELLINGS AND |
| STRUCTURES REGULATED BY THIS CODE. OTHER WIRING |
| METHODS, MATERIALS AND SUBJECT MATTER COVERED IN NFPA |
| 70 ARE ALSO ALLOWED BY THIS CODE". SECTION E3402.1 |
| STATES: "CHAPTERS 34 THROUGH 43 SHALL COVER THE |
| INSTALLATION OF ELECTRICAL SYSTEMS, EQUIPMENT AND |
| COMPONENTS INDOORS AND OUTDOORS THAT ARE WITHIN THE |
| SCOPE OF THIS CODE, INCLUDING SERVICES, POWER |
| DISTRIBUTION SYSTEMS, FIXTURES, APPLIANCES, DEVICES AND |
| APPURTENANCES. SERVICES WITHIN THE SCOPE OF THIS CODE |
| SHALL BE LIMITED TO 120/240-VOLT, 0- TO 400-AMPERE, |
| SINGLE-PHASE SYSTEMS. THESE CHAPTERS SPECIFICALLY COVER |
| THE EQUIPMENT, FIXTURES, APPLIANCES, WIRING METHODS AND |
| MATERIALS THAT ARE MOST COMMONLY USED IN THE |
| CONSTRUCTION OR ALTERATION OF ONE- AND TWO-FAMILY |
| DWELLINGS AND ACCESSORY STRUCTURES REGULATED BY THIS |
| CODE. THE OMISSION FROM THESE CHAPTERS OF ANY MATERIAL |
| OR METHOD OF CONSTRUCTION PROVIDED FOR IN THE |
| REFERENCED STANDARD NFPA 70 SHALL NOT BE CONSTRUED AS |
| PROHIBITING THE USE OF SUCH MATERIAL OR METHOD OF |
| CONSTRUCTION. ELECTRICAL SYSTEMS, EQUIPMENT OR |
| COMPONENTS NOT SPECIFICALLY COVERED IN THESE CHAPTERS |
| SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF NFPA |
| 70". SO, BASED ON THE FACT THAT THE RESIDENTIAL CODE |
| COVERS THE METHODS AND MATERIALS "MOST COMMONLY |
| ENCOUNTERED", AND THAT ANY "EQUIPMENT OR COMPONENTS NOT |
| SPECIFICALLY COVERED IN THESE CHAPTERS SHALL COMPLY |
| WITH THE APPLICABLE PROVISIONS OF NFPA 70", I ALWAYS |
| SUPPLY THE NEC SECTION NUMBERS IN ADDITION TO THE FBC |
| RESIDENTIAL CODE SECTIONS. I HOPE THIS ANSWERS YOUR |
| QUESTION. PLEASE FEEL FREE TO EMAIL ME IF YOU NEED |
| FURTHER EXPLANATION. |
| 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY. |
| THE SUBMITTED RISER SHOWS 3-#2 WIRES WITH A "BOND" TO |
| THE INTERIOR PANEL, WHICH IS STATED TO BE A 120 AMP |
| SERVICE. THE METER MAIN COMBO SPECIFIED ON THE PLAN |
| WILL NOT ACCEPT ANYTHING LARGER THAN A 100 AMP BREAKER |
| ON A 2-POLE SPACE, PER THE MANUFACTURERS SPEC SHEET. |
| ADDITIONALLY, 120 AMP IS NOT A RECOGNIZED FUSE/BREAKER |
| SIZE PER THE NEC OR THE FBC RESIDENTIAL. THEREFORE, THE |
| INTERIOR PANEL FEED WILL NEED TO BE SIZED FOR THE 150 |
| AMP MAIN BREAKER IN THE METER MAIN (USING THE FEED |
| THROUGH LUGS), OR A SMALLER SIZE BREAKER AND WIRE IF |
| THE LOAD CALCULATION PERMITS. ALSO, THE FEEDER TO THE |
| INTERIOR PANEL IS REQUIRED TO HAVE AN EQUIPMENT |
| GROUNDING CONDUCTOR PER CODE, NOT A "BOND". THERE |
| SHOULD NOT BE A "BOND", OR ANY OTHER GROUND WIRE IN THE |
| SERVICE LATERAL FROM THE POWER COMPANY. PROVIDE |
| CORRECTIONS AS PREVIOUSLY REQUESTED AND EXPLAINED |
| ABOVE. NEC 215.5, 240.6, 250.4(A), 250.24(A), |
| 310.15(B)(16); FBC RE3705.6, RE3705.1, RE3607.1, |
| RE3607.2, RE3704.6, RE3908.8, RE3908.12 |
| 3. PREVIOUS COMMENT #5 NOT ADDRESSED SATISFACTORILY. |
| THE NOTE CURRENTLY ON PLAN FOR AFCI PROTECTION DOES NOT |
| INCLUDE ALL AREAS THAT REQUIRE THIS PROTECTION. REVISE |
| NOTE OR ADD CODE SECTION TO STATEMENT TO REFLECT THE |
| REQUIREMENTS OF THE CODE. FBC 107.2.1, FBC RE3902.12; |
| NEC 210.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |