2017-07-17 12:16:17 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE CORRECTED PANEL SCHEDULE. CIRCUIT FOR WATER |
| HEATER SHOULD BE A 25 AMP BREAKER. NEC 215.5, 408.4, |
| 408.30, 422.13; FBC 107.2.1, FBC RE3706.1 |
| 2. RISER DIAGRAM SHOWS A 150 AMP SERVICE WITH # 1 WIRE |
| FEEDING THE INTERIOR PANEL. # 1 COPPER CAN ONLY BE USED |
| WHERE IT FEEDS 100% OF THE LOAD. PROVIDE CORRECTION. |
| NEC 310.15(B)(7); FBC RE3602.2 |
| 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| 4. LOAD CALCULATION SHOULD INCLUDE 1500 WATTS FOR THE |
| LAUNDRY CIRCUIT. NEC 220; FBC RE3602.2 |
| 5. PROVIDE AFCI PROTECTION. ALL 120-VOLT, SINGLE PHASE, |
| 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC 210.12, FBC |
| RE3902.12 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |