Notes
Date Text
2017-07-06 09:41:03720 8TH STREET
 TRACKING #17060169
 PERMIT #16060377
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **COMMENTS NOT ADDRESSED FROM PREVIOUS REVIEW.**
  
 SPRINKLER LOCATED 12 FEET FROM WALL OR MISSING
 SPRINKLER PROTECTION IN CLOSET #208, #221, AND #227.
  
 SPRINKLER COVERAGE IN STORAGE ROOM #218 EXCEEDS 130
 SQ.FT.
  
 FLOOR AREA BELOW 8'-0" AFF CEILING IS NOT PROTECTED BY
 THE EXTENDED COVERAGE SPRINKLER LOCATED IN THE 8'-6"
 CEILING FOR WORKROOM #232.
  