Plan Review Notes
Plan Review Notes For Permit 17060048
Permit Number 17060048
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-05 14:47:58THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE FA SHALL BE TESTED PER NFPA 72.
  
 14.4.1.2* REACCEPTANCE TESTING.
 14.4.1.2.1 REACCEPTANCE TESTING SHALL BE PERFORMED AS
 REQUIRED IN 14.4.1.2.1.1 THROUGH 14.4.1.2.1.4.
 14.4.1.2.1.1 WHEN AN INITIATING DEVICE, NOTIFICATION
 APPLIANCE, OR CONTROL RELAY IS ADDED, IT SHALL BE
 FUNCTIONALLY TESTED.
 14.4.1.2.1.2 WHEN AN INITIATING DEVICE, NOTIFICATION
 APPLIANCE, OR CONTROL RELAY IS DELETED, ANOTHER DEVICE,
 APPLIANCE, OR CONTROL RELAY ON THE CIRCUIT SHALL BE
 OPERATED.
 14.4.1.2.1.3 WHEN MODIFICATIONS OR REPAIRS TO CONTROL
 EQUIPMENT HARDWARE ARE MADE, THE CONTROL EQUIPMENT
 SHALL BE TESTED IN ACCORDANCE WITH TABLE 14.4.2.2,
 ITEMS 1(A) AND 1(D).
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  