2017-11-13 09:02:49 | 2ND REVIEW FBC-2014 MECHANICAL |
| PERMIT #17060032 |
| 11/13/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE 24X24 TRANSFER GRILL IS ALLOWING RECIRCULATION |
| OF AIR FROM THE SALON INTO THE OFFICE AREA WHICH IS |
| PROHIBITED PER TABLE 403.3 FOOTNOTE B. |
| |
| 2) THE PLAN DOES NOT SHOW THE REQUIRED SOURCE CAPTURE |
| SYSTEMS REQUIRED AT EACH MANI AND PEDI STATION, AND HOW |
| THE FUMES, VAPORS ETC. ARE BEING EXHAUSTED OUT OF THE |
| BUILDING. PLEASE SEE SECTION 501.3 WHICH REQUIRES THE |
| HEALTHY AIR SOURCE CAPTURE SYSTEMS TO BE DUCTED TO THE |
| OUTDOORS. PLEASE PROVIDE A MEDCHANICAL FLOOR PLAN |
| DRAWING THAT SHOWS THE STATIONS, THE SYSTEMS, THE |
| |
| DUCT RUNS, AND EXHAUST OUTLET LOCATIONS. INDICATE THE |
| TYPES AND SIZES OF EXHAUST DUCTS TO BE INSTALLED, AND |
| PROVIDE SUPPORT AND CONNECTION DETAILS. |
| |
| 3) THE SUBMITTED PRODUCT INFORMATION SHEETS FOR THE |
| HEALTHY AIR SYSTEMS DO NOT PROVIDE ANY LISTING OR |
| LABELING INFORMATION, OR INDICATE THAT THE PRODUCT HAS |
| BEEN TESTED AND APPROVED BY ANY AGENCIES SUCH AS ETL OR |
| UL. PLEASE SUBMIT PRODUCT DATA SHEETS WITH SHOP DRAWING |
| APPROVAL SIGNATURES BY THE ENGINEER OF RECORD. |
| |
| 4) PROVIDE EXHAUST VENTILATION CALCULATIONS, AND AIR |
| BALANCE CALCULATIONS. |
| |
| 5) PROVIDE A SEQUENCE OF OPERATION FOR EF-1- SEE |
| SECTION 501.4 |
| |
| 6) IT APPEARS THAT THE NEW CONDENSER IS BEING LOCATED |
| WITHIN 10' OF THE ROOF EDGE WHICH WOULD REQUIRE A GUARD |
| OR PARAPET AT A MINIMUM HEIGHT OF 42"- PLEASE COMPLY. |
| PLEASE NOTE THAT PERMANENT LADDERS ARE REQUIRED FOR |
| ROOF TOP MECHANICAL EQUIPMENT LOCATED OVWER 16' FROM |
| GRADE. |
| |
| 7) THE ARCHITECTURAL PLANS ARE INDICATING THE AHU-1 |
| CLOSET DOOR IS WOOD, HOWEVER AC CLOSET DOORS SHALL BE |
| NON-COMBUSTIBLE IN COMPLIANCE WITH SECTION C403.2.7.2 |
| FBC-14 ENERGY CONSERVATION AND SECTION 602 FBC-14 |
| MECHANICAL. PLEASE NOTE THAT THE NO CLOSET WALLS OR |
| DOOR ARE SHOWN FOR AHU-2 ALTHOUGH THERE IS A NOTE ON |
| THE PLAN INDICATING A LOUVERED DOOR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |