2017-11-14 09:30:12 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17060032 |
| ADD: 444 25TH STREET / UNIT: 3 |
| CONT: H. LAYTON MAINGUY |
| TEL: 954-249-8500 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. NOV. 14/2017 |
| ACTION: DENIED |
| |
| 1) THE COVERSHEET A-1.0: |
| 1A-D) COMPLIED. |
| |
| 1E) 2ND REQUEST. THE PLANS HAVE NO SATISFIED THE |
| MECHANICAL COMMENTS MAY REQUIRE ADDITIONAL MECHANICAL |
| EQUIPMENT EITHER ON THE ROOF OR THROUGH THE WALL. SCOPE |
| OF WORK INCLUDES WORK IN A HAIR SALON THAT CONSISTS OF |
| THE FOLLOWING AREAS: SHAMPOOS, PEDICURES, NAIL |
| POLISHING, WAXING, AND HAIR STYLING. YOU WILL RECEIVE |
| COMMENTS FROM THE MECHANICAL PLANS REVIEWER ON THE |
| FRESH AIR AND EXHAUST AIR THAT WILL BE REQUIRED FOR |
| PEDICURES AND NAIL POLISHING. PLEASE BE AWARE THAT |
| EITHER THE FRESH AIR OR EXHAUST AIR WILL BE THROUGH THE |
| ROOF AND MAY REQUIRE ADDITIONAL ROOF FRAMING, ANCHORING |
| OF ROOF TOP CURBS AND INTAKE AND EXHAUST FANS. NONE OF |
| THIS INFORMATION HAS BEEN PROVIDED FOR THIS REVIEW. |
| FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF |
| TOP FANS |
| (G) PRE-ENGINEERED A/C STANDS (POSSIBLY) |
| |
| 2) SEMI COMPLIED. THE PLANS PROVIDE THE WIND SPEED OF |
| 170 VULT, IMPORTANCE FACTOR OF 1.0, BUILDING RISK |
| CATEGORY LL AND EXPOSURE C. THE NOMENCLATURE 160 VUIC |
| AND 124 VAST ARE UNKNOWN TERMS. |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| IF THE DESIGNER IS TRYING TO INTERPOLATE BETWEEN |
| CONTOUR LINES FOR FIGURE 1609A THE 160 VULT CONTOUR |
| LINE IS FURTHER WEST THAN THE CITY LIMITS FOR WEST PALM |
| BEACH. INTERPOLATION FOR THIS LOCATION WOULD BE 168 |
| VULT AND 130 VASD. |
| |
| 3) SHEET A-1.1 SECTION 1 INDICATES A RAISED PLATFORM 11 |
| INCHES FROM THE FLOOR. |
| 3A-B) COMPLIED. |
| |
| 3C) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE USE |
| OF A PORTABLE PEDICURE SPA IT SHOWS COMPLIANCE WITH THE |
| 2014 ACCESSIBILITY CODE SECTION 103 EQUIVALENT |
| FACILITATION. |
| PLEASE PROVIDE HOW A PERSON IN A WHEEL CHAIR IS GOING |
| TO ACHIEVE ACCESS TO THE CHAIR ON THE PLATFORM. |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2014 FBC-ACCESS. CODE 202.3 ALTERATIONS. WHERE EXISTING |
| ELEMENTS OR SPACES OR COMMON AREAS ARE ALTERED, EACH |
| ALTERED ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE |
| APPLICABLE REQUIREMENTS OF CHAPTER 2 AND SECTION |
| 201.1.1. |
| 2014 ACCESS. CODE. 201.1.1 VERTICAL ACCESSIBILITY. |
| SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS |
| FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| BUILDING, STRUCTURE OR FACILITY. |
| |
| 4) THE VALUE OF THE PROJECT MAY BE INCREASED BECAUSE OF |
| THE REQUIRED, INTAKE AND EXHAUST AIR, FRAMING AND ROOF |
| TOP MECHANICAL EQUIPMENT. WITH THE INCREASED VALUE THE |
| VALUE OF THE PROJECT WILL BE OVER $2,500.00 IN VALUE |
| REQUIRING NOTARIZED SIGNATURE THE CONTRACTOR. |
| |
| 5) 2ND REQUEST. THE PLANS DO NOT INDICATE TRYING TO |
| MAKE ANY ACCESSIBLE UPGRADES PLEASE REVIEW THE |
| FOLLOWING: |
| 2014 FBC-ACCESS. CODE: |
| 202.4.3 SERIES OF SMALLER ALTERATIONS. THE OBLIGATION |
| TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY NOT BE |
| EVADED BY PERFORMING A SERIES OF SMALL ALTERATIONS TO |
| THE AREA SERVED BY A SINGLE PATH OF TRAVEL IF THOSE |
| ALTERATIONS COULD HAVE BEEN PERFORMED AS A SINGLE |
| UNDERTAKING. |
| |
| NEW COMMENT IN REGARDS TO DISPROPORTIONALITY. PLEASE |
| NOTE SHEET A1.0 DOOR #4 IN THE OFFICE IS BEING REMOVE |
| DOOR. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION SECTION 104.9.1 USED MATERIALS AND |
| EQUIPMENT. THE USE OF USED, RECYCLED, OR RECLAIMED |
| MATERIALS WHICH MEET THE REQUIREMENTS OF THIS CODE FOR |
| NEW MATERIALS IS PERMITTED. USED |
| EQUIPMENT AND DEVICES SHALL NOT BE REUSED UNLESS |
| APPROVED BY THE BUILDING OFFICIAL. |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. DOOR # 4 NEEDS TO BE A |
| 36 INCH WIDE DOOR THAT WILL PROVIDE THE REQUIRED 32 |
| INCHES CLEAR. THIS DOOR WOULD ALSO QUALIFY FOR THE 20 % |
| DISPROPORTIONATE COST, THE GRAB BARS DOESN?T SINCE |
| THERE IS AN EXISTING 2 FOOT WIDE DOOR, AND NOT BEING |
| REPLACED. A WHEELCHAIR BOUND PERSON CODE NOT GET IN THE |
| RESTROOM. |
| |
| 202.4.3.1 IF AN AREA CONTAINING A PRIMARY FUNCTION HAS |
| BEEN ALTERED WITHOUT PROVIDING AN ACCESSIBLE PATH OF |
| TRAVEL TO THAT AREA, AND SUBSEQUENT ALTERATIONS OF THAT |
| AREA, OR A DIFFERENT AREA ON THE SAME PATH OF TRAVEL, |
| ARE UNDERTAKEN WITHIN THREE YEARS OF THE ORIGINAL |
| ALTERATION, THE TOTAL COST OF ALTERATIONS TO THE |
| PRIMARY FUNCTION AREAS ON THAT PATH OF TRAVEL DURING |
| THE PRECEDING THREE YEAR PERIOD SHALL BE CONSIDERED IN |
| DETERMINING WHETHER THE COST OF MAKING THAT PATH OF |
| TRAVEL ACCESSIBLE IS DISPROPORTIONATE. |
| |
| 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO |
| PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED |
| AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL |
| ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE |
| ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY |
| BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS |
| ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS |
| ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS |
| INSTALLING GRAB BARS, ENLARGING TOILET STALLS, |
| INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET |
| CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING |
| ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE |
| TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION |
| DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV) |
| COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE |
| DRINKING FOUNTAIN. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |