Plan Review Notes
Plan Review Notes For Permit 17060032
Permit Number 17060032
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-08 13:11:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17060032
 6/8/17
  
 RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR THE
 PROPOSED BEAUTY/NAIL SALON. PLEASE PROVIDE PLANS,
 DETAILS, AND SPECIFICATIONS FOR ALL HVAC ALTERATIONS
 AND INSTALLATIONS REQUIRED TO ACCOMODATE THE NEW
 OCCUPANCY AS OUTLINED IN SECTION 403 AND TABLE 403.3
 FBC-14 MECHANICAL. PLEASE NOTE THAT MECHANICAL EXHAUST
 SYSTEMS ARE REQUIRED AND RECIRCULATION OF AIR
  
 FROM THE SALON OR NAIL STATIONS IS PROHIBITED- SEE
 SECTION 403.2.1 ITEM 3. SEE REQUIREMENTS LISTED BELOW.
  
 A) PROVIDE EXHAUST VENTILATION SYSTEMS FOR THE MANICURE
 TABLES AND THE PEDICURE CHAIRS AT A RATE NOT LESS THAN
 50 CFMS PER NAIL STATION. EACH STATION SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM- SEE FOOTNOTE H
 UNDER TABLE 403.3. RECIRCULATION OF THE EXHAUST AIR IS
 PROHIBITED- FOOTNOTE B
  
 B) PROVIDE EXHAUST VENTILATION SYSTEM FOR THE BEAUTY
 SALON AT AN EXHAUST RATE OF 0.6 CFMS PER SF- TABLE
 403.3.
  
 C) PROVIDE A MEANS OF MAKEUP AIR FOR THE EXHAUST
 SYSTEMS- 501.4.
  
 D) CALCULATIONS REQUIRED: EXHAUST, OUTDOOR AIR FOR ALL
 OCCUPIED ROOMS AND SPACES, AND AIR BALANCE.
  
 E) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC
 SYSTEM THAT LISTS THE MAKE AND MODEL AND COOLING AND
 HEATING CAPACITIES OF THE SYSTEM.
  
 2) PLEASE SEE BUILDING REVIEW COMMENTS #1E AND #2 FOR
 EXTERIOR MECHANICAL EQUIPMENT AND APPLIANCE
 INSTALLATION REQUIREMENTS.
  
 3) PLEASE NOTE FURTHER COMMENTS MAY FOLLOW THIS REVIEW
 AFTER CORRECTED AND REVISED PLANS ARE RESUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  