Plan Review Notes
Plan Review Notes For Permit 17060032
Permit Number 17060032
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-07 14:23:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.1 - THE DOOR SWING FROM THE OFFICE/STAFF
 ROOM INTO THE HALLWAY CHANGES FROM SHEET A 1.0 & A 1.1.
 WHICH ONE IS CORRECT AND CORRECT THE OTHERS. IT IS
 IMPORTANT TO NOTE THAT SHEET A 1.1 SHOWS IT AS NOT
 BLOCKING THE HALLWAY.
  
 PLEASE CLARIFY.
  
  
  
  
 2) SHEET A 1.0 - THE OCCUPANCY IS INDICATED AS
 BUSINESS; HOWEVER, A STORAGE AREA IS INDICATED.
  
 PER NFPA 101, CHAPTER 6 CLASSIFICATION OF OCCUPANCY AND
 HAZARD OF CONTENTS
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE
 RESISTANCE?RATED ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED,
 UNLESS SEPARATE SAFEGUARDS ARE APPROVED.
 6.1.14.4 SEPARATED OCCUPANCIES.
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE BUILDING COMPRISING A DISTINCT
 OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE
 COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2,
 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE
 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY
 APPROVED EXISTING SEPARATIONS.
  
 PLEASE CLARIFY YOUR OCCUPANCY.
  
  
  
  
 3) SHEET A 1.1 - A BARN DOOR IS INDICATED AT THE
 HALLWAY IN THE CENTER OF THE OCCUPANCY AND IN THE EXIT
 PATH OF TRAVEL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS,
  
 7.2.1.14 HORIZONTAL-SLIDING DOOR ASSEMBLIES.
 HORIZONTAL-SLIDING DOOR ASSEMBLIES SHALL BE PERMITTED
 IN MEANS OF EGRESS, PROVIDED THAT ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE DOOR LEAF IS READILY OPERABLE FROM EITHER SIDE
 WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
 (2) THE FORCE THAT, WHEN APPLIED TO THE OPERATING
 DEVICE IN THE DIRECTION OF EGRESS, IS REQUIRED TO
 OPERATE THE DOOR LEAF IS NOT MORE THAN 15 LBF (67 N).
 (3) THE FORCE REQUIRED TO OPERATE THE DOOR LEAF IN THE
 DIRECTION OF TRAVEL IS NOT MORE THAN 30 LBF (133 N) TO
 SET THE LEAF IN MOTION AND IS NOT MORE THAN 15 LBF (67
 N) TO CLOSE THE LEAF OR OPEN IT TO THE MINIMUM REQUIRED
 WIDTH.
 (4) THE DOOR LEAF IS OPERABLE USING A FORCE OF NOT MORE
 THAN 50 LBF (222 N) WHEN A FORCE OF 250 LBF (1100 N) IS
 APPLIED PERPENDICULARLY TO THE LEAF ADJACENT TO THE
 OPERATING DEVICE, UNLESS THE DOOR OPENING IS AN
 EXISTING HORIZONTAL-SLIDING EXIT ACCESS DOOR ASSEMBLY
 SERVING AN AREA WITH AN OCCUPANT LOAD OF FEWER THAN 50.
 (5) THE DOOR ASSEMBLY COMPLIES WITH THE FIRE PROTECTION
 RATING, IF REQUIRED, AND, WHERE RATED, IS SELF-CLOSING
 OR AUTOMATICCLOSING BY MEANS OF SMOKE DETECTION IN
 ACCORDANCE WITH 7.2.1.8 AND IS INSTALLED IN ACCORDANCE
 WITH NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
 PROTECTIVES.
 (6) THE DOOR SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 PLEASE REVIEW FOR COMPLIANCE AND PROVIDE DETAILS.
  
  
  
 4) SHEET A 1.2 - THERE IS NO EXIT SIGN IN THE HALLWAY
 LEADING TO THE FRONT EXIT. IN THE EVENT THAT THE DOES
 COMPLY WITH ABOVE AND THEY ARE CLOSED THERE IS NO EXIT
 INDICATORS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) SHEET A 1.2 - THERE IS EXITING INDICATED FROM A
 BUSINESS AREA THROUGH A STORAGE OCCUPANCY. EXITING
 CANNOT PASS THROUGH AN AREA FORM A LOWER HAZARD
 (BUSINESS) THROUGH A HIGHER HAZARD (STORAGE.
  
 PER NFPA CHAPTER 7, 7.5.1.6 EXIT ACCESS FROM ROOMS OR
 SPACES SHALL BE PERMITTED TO BE THROUGH ADJOINING OR
 INTERVENING ROOMS OR AREAS, PROVIDED THAT SUCH ROOMS OR
 AREAS ARE ACCESSORY TO THE AREA SERVED. FOYERS,
 LOBBIES, AND RECEPTION ROOMS CONSTRUCTED AS REQUIRED
 FOR CORRIDORS SHALL NOT BE CONSTRUED AS INTERVENING
 ROOMS. EXIT ACCESS SHALL BE ARRANGED SOTHAT IT IS NOT
 NECESSARY TO PASS THROUGH ANY AREA IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 6) ALL SHEETS - THERE IS A PLATFORM WITH TWO STEPS
 INDICATED. THERE IS LITTLE TO NO DETAIL ON THESE STEPS.
  
 PEOPLE MUST EGRESS DOWN THESE STEPS TO EXIT THE
 OCCUPANCY. PER NFPA 101, CHAPTER 7, 7.2.2.4 GUARDS AND
 HANDRAILS.
 7.2.2.4.1 HANDRAILS.
 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON
 BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5
 OR 7.2.2.4.1.6.
 7.2.2.4.1.2 IN ADDITION TO THE HANDRAILS REQUIRED AT
 THE SIDES OF STAIRS BY 7.2.2.4.1.1, BOTH OF THE
 FOLLOWING PROVISIONS SHALL APPLY:
 (1) FOR NEW STAIRS, HANDRAILS SHALL BE PROVIDED WITHIN
 30 IN. (760 MM) OF ALL PORTIONS OF THE REQUIRED EGRESS
 WIDTH.
 (2) FOR EXISTING STAIRS, HANDRAILS SHALL MEET THE
 FOLLOWING CRITERIA:
 (A) THEY SHALL BE PROVIDED WITHIN 44 IN. (1120 MM) OF
 ALL PORTIONS OF THE REQUIRED EGRESS WIDTH.
 (B) SUCH STAIRS SHALL NOT HAVE THEIR EGRESS CAPACITY
 ADJUSTED TO A HIGHER OCCUPANT LOAD THAN PERMITTED BY
 THE CAPACITY FACTOR IN TABLE 7.3.3.1 IF THE STAIR?S
 CLEAR WIDTH BETWEEN HANDRAILS EXCEEDS 60 IN. (1525 MM).
 7.2.2.4.1.3 WHERE NEW INTERMEDIATE HANDRAILS ARE
 PROVIDED IN ACCORDANCE WITH 7.2.2.4.1.2, THE MINIMUM
 CLEAR WIDTH BETWEEN HANDRAILS SHALL BE 20 IN. (510 MM).
 7.2.2.4.1.4* THE REQUIRED EGRESS WIDTH SHALL BE
 PROVIDED ALONG THE NATURAL PATH OF TRAVEL.
 7.2.2.4.1.5 IF A SINGLE STEP OR A RAMP IS PART OF A
 CURB THAT SEPARATES A SIDEWALK FROM A VEHICULAR WAY, IT
 SHALL NOT BE REQUIRED TO HAVE A HANDRAIL.
  
 PLEASE REVIEW, CLARIFY OR CORRECT.
  
  
  
 7) SHEET A 1.2 - THERE IS NO DOOR SCHEDULE INDICATING
 SIZE, LOCKS OR LATCHES, OR HARDWARE.
  
 PLEASE PROVIDE.
  
  
 8) SHEET A 1.2 - THERE IS AN EXIT DOOR INDICATED AT THE
 REAR OF THE OCCUPANCY; HOWEVER, IT IS NO CLEAR IF THIS
 EXIT LEADS TO A PUBLIC WAY.
  
 PLEAASE PROVIDE A PROPERTY SITE PLAN INCLUDING ANY
 FENCING OR WALL DETAILS THAT MAY RESTRICT ACCESS TO A
 PUBLIC WAY.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL