Plan Review Notes
Plan Review Notes For Permit 17060032
Permit Number 17060032
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-09 07:40:20CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INDICATE ANY
 EXISTING SERVICE AND ANY UPGRADES AS NECESSARY. PROVIDE
 FLOOR PLAN SHOWING LOCATIONS OF ALL OUTLETS AND
 LIGHTING, NEW AND EXISTING. PROVIDE RISER DIAGRAM AND
 PANEL SCHEDULE WITH WIRE AND CONDUIT SIZING. PROVIDE
 SPEC SHEETS FOR EQUIPMENT. FBC 107.2.1, 107.3.5, NEC
 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  