1 |
|
Notes |
Date |
Text |
2017-06-09 07:40:20 | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | ELECTRICAL REVIEW COMMENTS: | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. INDICATE ANY | | EXISTING SERVICE AND ANY UPGRADES AS NECESSARY. PROVIDE | | FLOOR PLAN SHOWING LOCATIONS OF ALL OUTLETS AND | | LIGHTING, NEW AND EXISTING. PROVIDE RISER DIAGRAM AND | | PANEL SCHEDULE WITH WIRE AND CONDUIT SIZING. PROVIDE | | SPEC SHEETS FOR EQUIPMENT. FBC 107.2.1, 107.3.5, NEC | | 110.3 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|