Plan Review Notes
Plan Review Notes For Permit 17060032
Permit Number 17060032
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-05 17:28:022014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17060032
 ADD: 444 25TH STREET / UNIT: 3
 CONT: H. LAYTON MAINGUY
 TEL: 954-249-8500
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 05/2017
 ACTION: DENIED
  
 1) THE COVERSHEET A-1.0:
 1A) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHICH
 COMPLIANCE METHOD THE PLANS WERE DESIGNED TOO?
 2014 FBC-EXISTING BUILDING CODE :
 301.1.1 PRESCRIPTIVE COMPLIANCE METHOD.
 301.1.2 WORK AREA COMPLIANCE METHOD.
 301.1.3 PERFORMANCE COMPLIANCE METHOD.
  
 1B) SHEET A-1.0 INDICATES THE CONSTRUCTION TYPE AS TYPE
 III? IS THIS A OR B? FBC-B TABLE 503.
 1C) THE PLANS INDICATE THE USE AS A BEAUTY PARLOR/
 BUSINESS OCCUPANCY. PLEASE NOTE THE TOTAL SQUARE
 FOOTAGE IS 1740 SQ. FT. THIS TENANT SPACE. THE STORE
 AREA IS 199.3 SQ. FT. OR OVER THE 10 % FLOOR AREA OF
 THE TENANT SPACE. TO LOOK AT ACCESSORY OCCUPANCIES
 VERSES MIXED USE OCCUPANCIES YOU TAKE THE TOTAL FLOOR
 AREA OF THE BUILDING, NOT THE TENANT SPACE. SEE FBC-B
 508.2.1 AREA LIMITATIONS.
 B 508.2.1 AREA LIMITATIONS. AGGREGATE ACCESSORY
 OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF
 THE BUILDING AREA OF THE STORY IN WHICH THEY ARE
 LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN
 TABLE 503, WITHOUT BUILDING AREA INCREASES IN
 ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY
 OCCUPANCIES.
 1D) OCCUPANT LOADS. PLEASE NOTE IN THE OCCUPANT LOAD
 CALCULATIONS THERE ARE 15.4 AND 0.7 OCCUPANTS. PLEASE
 NOTE YOU ONLY COUNT WHOLE OCCUPANTS, YOU ALWAYS ROUND
 UP. THERE ARE NO PARTIAL OCCUPANTS. FLORIDA BUILDING
 CODE INFORMAL INTERPRETATION REPORT # 5479 SECTION
 1004.1.2.
 1E) SCOPE OF WORK INCLUDES WORK IN A HAIR SALON THAT
 CONSIST OF THE FOLLOWING AREAS: SHAMPOOS, PEDICURES,
 NAIL POLISHING, WAXING, AND HAIR STYLING. YOU WILL
 RECEIVE COMMENTS FROM THE MECHANICAL PLANS REVIEWER ON
 THE FRESH AIR AND EXHAUST AIR THAT WILL BE REQUIRED FOR
 PEDICURES AND NAIL POLISHING. PLEASE BE AWARE THAT
 EITHER THE FRESH AIR AND EXHAUST AIR WILL BE THROUGH
 THE ROOF AND MAY REQUIRE ADDITIONAL ROOF FRAMING,
 ANCHORING OF ROOF TOP CURBS AND INTAKE AND EXHAUST
 FANS. NONE OF THIS INFORMATION HAS BEEN PROVIDED FOR
 THIS REVIEW.
 FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF
 TOP FANS
 (G) PRE-ENGINEERED A/C STANDS (POSSIBLY)
  
 2) FOR THE ROOF TOP MECHANICAL EQUIPMENT PLEASE PROVIDE
 THE WIND DESIGN CRITERIA, 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2.2. RISK CATEGORY.
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) SHEET A-1.1 SECTION 1 INDICATES A RAISED PLATFORM 11
 INCHES FROM THE FLOOR.
 3A) PLEASE NOTE THE 2 STAIRS ARE NOT THE SAME IN
 HEIGHT. 2014 FBC-B 1009.7.4 DIMENSIONAL UNIFORMITY.
  
 3B) THE PLATFORM SECTION SHOWS THE USE OF 2 X2 WOOD
 JOIST AT 16 INCHES ON CENTER. PLEASE REVIEW THE
 VERTICAL DIMENSION I BELIEVE IT IS MISLABELED, A TYPO,
 PLEASE CORRECT. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3C) PLEASE PROVIDE HOW A PERSON IN A WHEEL CHAIR IS
 GOING TO ACHIEVE ACCESS TO THE CHAIR ON THE PLATFORM.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2014 FBC-ACCESS. CODE 202.3 ALTERATIONS. WHERE EXISTING
 ELEMENTS OR SPACES OR COMMON AREAS ARE ALTERED, EACH
 ALTERED ELEMENT, SPACE OR AREA SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF CHAPTER 2 AND SECTION
 201.1.1.
 2014 ACCESS. CODE. 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 4) THE VALUE OF THE PROJECT MAY BE INCREASED BECAUSE OF
 THE REQUIRED, INTAKE AND EXHAUST AIR, FRAMING AND ROOF
 TOP MECHANICAL EQUIPMENT. WITH THE INCREASED VALUE THE
 VALUE OF THE PROJECT WILL BE OVER $2,500.00 IN VALUE
 REQUIRING NOTARIZED SIGNATURE THE CONTRACTOR.
  
 5) THE PLANS DO NOT INDICATE TRYING TO MAKE ANY
 ACCESSIBLE UPGRADES PLEASE REVIEW THE FOLLOWING:
 2014 FBC-ACCESS. CODE:
 202.4.3 SERIES OF SMALLER ALTERATIONS. THE OBLIGATION
 TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY NOT BE
 EVADED BY PERFORMING A SERIES OF SMALL ALTERATIONS TO
 THE AREA SERVED BY A SINGLE PATH OF TRAVEL IF THOSE
 ALTERATIONS COULD HAVE BEEN PERFORMED AS A SINGLE
 UNDERTAKING.
  
 202.4.3.1 IF AN AREA CONTAINING A PRIMARY FUNCTION HAS
 BEEN ALTERED WITHOUT PROVIDING AN ACCESSIBLE PATH OF
 TRAVEL TO THAT AREA, AND SUBSEQUENT ALTERATIONS OF THAT
 AREA, OR A DIFFERENT AREA ON THE SAME PATH OF TRAVEL,
 ARE UNDERTAKEN WITHIN THREE YEARS OF THE ORIGINAL
 ALTERATION, THE TOTAL COST OF ALTERATIONS TO THE
 PRIMARY FUNCTION AREAS ON THAT PATH OF TRAVEL DURING
 THE PRECEDING THREE YEAR PERIOD SHALL BE CONSIDERED IN
 DETERMINING WHETHER THE COST OF MAKING THAT PATH OF
 TRAVEL ACCESSIBLE IS DISPROPORTIONATE.
  
 202.4.1 DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COSTS THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  