Plan Review Notes
Plan Review Notes For Permit 17051249
Permit Number 17051249
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-09 08:27:36PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LWC-34 SYSTEM FOR THE LIGHTWEIGHT CONCRETE DECK
 HAS A MAXIMUM DESIGN PRESSURE OF -60.0 PSF. THIS IS NOT
 ADEQUATE FOR THE PERIMETER AND CORNER AREAS. SUBMIT
 ENHANCED FASTENING CALCULATIONS THAT HAVE BEEN SIGNED
 AND SEALED BY A FLORIDA LICENSED DESIGN PROFESSIONAL.
 SEE LIMITATION NUMBER 5.7 ON PAGE 5 OF PRODUCT APPROVAL
 FL2533.
  
 2) SUBMIT TWO SETS OF A MOISTURE SURVEY OF THE
 LIGHTWEIGHT CONCRETE DECK. FBC 1510 & FBC 1917
  
 3) SUBMIT TWO SETS OF A FASTENER WITHDRAWAL TESTING FOR
 THE LIGHTWEIGHT CONCRETE DECK. SEE LIMITATION NUMBER
 5.9 ON PAGE 5.