Plan Review Notes
Plan Review Notes For Permit 17051098
Permit Number 17051098
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-30 08:35:071ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051098
 5/30/17
  
 1) SHEET M-1: CLARIFY HOW AIR IS BEING RETURNED TO THE
 EXISTING RTU'S.
  
 2) M-1: PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING
 RTU'S.
  
 3) M-1: PROVIDE A HEADING ABOVE THE JOHNSON CONTROLS
 EQUIPMENT SCHEDULE TO IDENTIFY THE NEW SYSTEM.
  
 4) M-1: CLARIFY IF THE EXISTING RTU'S HAVE DUCT SMOKE
 DETECTORS INSTALLED IN THE AIR STREAMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER