Plan Review Notes For Permit 17051057 |
Permit Number |
17051057 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-10-20 14:26:55 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17051057 | | 10/20/2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SUBMITTED S-1 ENGINEERING SHEET FOR THE CARRIER | | CHASISS APPEARS TO BE PART OF A MIAMI-DADE NOA. PLEASE | | SUBMIT THE ENTIRE NOA INCLUDING THE COVER SHEET. IF | | THIS IS NOT PART OF AN NOA THEN AN ORIGINAL SIGNATURE | | AND SEAL BY THE ENGINEER IS REQUIRED- SECTION | | 61G15-23.002 FAC. | | | | 2) THE WIND LOAD CALCULATIONS BY LARRY VAN DYK REQUIRE | | AN ENGINEER'S SEAL AND SIGNATURE PER SECTION 1609 | | FBC-14 BUILDING AND FLORIDA STATUTE 471. | | | | 3) PLEASE SHOW THE LOCATION OF THE AC STAND AND WHICH | | AC CONDENSER IS BEING MOUNTED TO IT. | | | | 4) THE RETURN TRANSFER DUCT FROM THE LAUNDRY ROOM TO | | THE CORRIDOR IS PROHIBITED PER SECTION 601.2- CORRIDORS | | CANNOT BE USED TO RETURN AIR | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|