2017-10-20 07:47:45 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17051057 |
| ADD: 4300 MILLER AVE. |
| CONT: CANO INC. |
| TEL:561-543-1290 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: FRI. OCT. 20/ 2017 |
| ACTION: DENIED |
| |
| BUILDING # 3/ OFFICE. |
| |
| 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B) |
| |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| |
| |
| 1) 2ND REQUEST. RESPONSE ACKNOWLEDGED WILL BE SIGNED BY |
| OWNER. PLEASE NOTE THE OWNER OF 4300 MILLER AVE. WILL |
| NEED TO SIGN THE PERMIT APPLICATION. THE PALM BEACH |
| COUNTY PROPERTY APPRAISERS OFFICE LIST TC & MARILYN |
| DALESSANDRO AS THE OWNERS. 2014 FLORIDA BUILDING CODE W |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION |
| 105.1 PERMIT REQUIRED. |
| |
| 2) 2ND REQUEST. RESPONSE ACKNOWLEDGED SURVEY WILL BE |
| SUBMITTED BY OWNER. PLEASE PROVIDE A SURVEY FOR THIS |
| LOT IT APPEARS THE BUILDING IS CLOSER THAN 3 FEET TO |
| THE PROPERTY LINE. IT APPEARS THE BUILDING MAYBE ON THE |
| PROPERTY LINE SEE PALM BEACH COUNTY PROPERTY APPRAISERS |
| OFFICE MAP. THE EXTERIOR WALL ADJACENT TO THE PROPERTY |
| LINE WILL NEED TO SHOW COMPLIANCE WITH 2014 FBC-B TABLE |
| 602, 1 HOUR FIRE RATING. |
| |
| 3) COMPLIED. SHEET A-103 SHOWS WASHER AND DRYERS. |
| |
| 4) COMPLIED. SHEET A403 DETAIL # 6 IS FOR THE |
| ACCESSIBLE RESTROOM . |
| |
| 5) 2ND REQUEST OWNER TO PROVIDE SITE PLAN. SHEET A103 |
| THE FLOOR PLAN DOES NOT INDICATE IF THE 2 ENTRIES INTO |
| THE BUILDING ARE LEVEL WITH THE EXTERIOR OF THE |
| BUILDING AND COMPLYING WITH 2014 FBC-ACCESS. CODE 402.2 |
| COMPONENTS. ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR |
| MORE OF THE FOLLOWING COMPONENTS: WALKING SURFACES WITH |
| A RUNNING SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, |
| CURB RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND |
| PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE |
| SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF |
| CHAPTER 4 AND 208.3.1. |
| |
| 6) 2ND REQUEST. OWNER TO PROVIDE SITE PLAN. PLEASE |
| SUBMIT A SITE PLAN AND SHOW COMPLIANCE WITH AN |
| ACCESSIBLE PARKING SPACE AND ACCESS AISLE WHERE THE |
| OCCUPANT WILL BE ABLE TO TRAVEL FROM THE VEHICLE TO THE |
| FRONT ENTRY. ACCESS. CODE 502.2 VEHICLE SPACES. EACH |
| PARKING SPACE MUST BE AT LEAST 12 FEET (3658 MM) WIDE, |
| SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN |
| ADJACENT ACCESS AISLE COMPLYING WITH 502.3. |
| |
| 7) 2ND REQUEST. RESPONSE INDICATES DISCUSSION WITH |
| STRUCTURAL ENGINEER, WE WILL NEED A SIGNED AND SEALED |
| LETTER FOR THE STRUCTURAL ANALYSIS FOR THE OPENING OF |
| THE ROOF DECK, AND IF REINFORCEMENT IS NECESSARY, HOW |
| THE ROOF TOP CURB WILL BE ATTACHED TO THE ROOF DECK AND |
| THE ROOF TOP UNIT TO THE CURB. |
| COMPUTER CALCULATIONS FOR WIND DESIGN, MWFRS AND |
| COMPONENTS AND CLADDING WERE SUBMITTED BY LARRY VAN |
| DYK, WHO IS THIS THE CALCULATIONS ARE NOT SIGNED NOR |
| SEALED. |
| 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH |
| LISTED PAGES OR INDEX SHEET FOR ENGINEERING |
| SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| PREPARATION OF EACH SECTION OF THE ENGINEERING |
| SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER |
| THE COVER SHEET OR INDEX SHEET. |
| |
| 1ST ROUND OF COMMENTS. SHEET A-501 DETAIL # 9 NEW CURB |
| AT EXISTING ROOF. THIS APPEARS TO BE A NEW ROOF TOP |
| OPENING THAT WILL BE CUT INTO THE CONCRETE ROOF DECK. |
| THERE IS NO DETAILS AS TO REQUIRED REINFORCEMENT NOR |
| LOCATION IN REGARDS TO THE CONCRETE JOIST. THE DETAIL |
| WILL ALSO NEED TO PROVIDE A WIND ANALYSIS FOR THE |
| ANCHORING OF THE CURB TO THE ROOF DECK AS WELL AS THE |
| RTU TO THE CURB. 2014 FBC-B 1604.4 ANALYSIS. LOAD |
| EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS |
| SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS |
| THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, |
| GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM |
| MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| WIND LOADS. |
| |
| 7A) NEW COMMENT. SUBMITTED MIAMI-DADE NOA 12-0327.02 |
| EXPIRED 06/28/2017 SUBMIT SUPERSEDED NOA. |
| |
| 7B) NEW COMMENT. THE ROOF TOP A/C STAND PRODUCT |
| APPROVAL A MIAMI-DADE NOA # 12-0327.02 WAS SUBMITTED, |
| PROVIDE SUPERSEDED NOA, THIS ONE IS EXPIRED, NEEDS TO |
| BE REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY |
| THE FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE |
| VIEW) OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON |
| STAND, THE MEAN ROOF HEIGHT OF THE STAND AND |
| COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN |
| THE TABLES, ANCHORS AND UPLIFT VERSES MOMENT FOR THE |
| UNIT TO THE STAND AND THE STAND TO THE ROOF. THE |
| PRODUCT APPROVAL IS TO BE REVIEWED BY THE DESIGNER OF |
| RECORD, APPROVED BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. |
| |
| 7C) NEW COMMENT. ATTACHED WITH THE NEW PRODUCT APPROVAL |
| FOR THE ROOF TOP A/C STAND IS A CARRIER ATTACHMENT |
| DETAIL BY ROBERT SAMARA P.E. PLEASE NOTE THIS SIGNED |
| AND SEALED DOCUMENT IS DATED 11/11/15. THIS SEEMS TO BE |
| A GENERIC DETAIL. THE SEAL IS MINIATURIZED AND A COPY |
| OF SIGNATURE. |
| 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| 2006. |
| 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED |
| BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| IS PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| |
| 7D) NEW COMMENT. MIAMI-DADE NOA 15-0923.04 RUSKIN |
| ALUMINUM LOVER HAS NOT BEEN REVIEWED BY THE DESIGNER OF |
| RECORD. W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |