Plan Review Notes For Permit 17051057 |
Permit Number |
17051057 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-30 17:19:33 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17051057 | | 5/30/17 | | | | RESULTS: DENIED. | | | | 1) THE SUBMITTED ENERGYGAUGE SUMMIT@FLA/COM-2010, FORM | | 506-2010 IS OUTDATED. PLEASE SUBMIT TWO COPIES OF THE | | FLA/COM-2015 VERSION WITH THE CERTIFICATIONS AND | | MANDATORY REQUIREMENTS CHECKLISTS COMPLETED. | | | | 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | SYSTEM OF RTU-1, UNLESS MANUFACTURER'S DATA INDICATES | | THAT THE SYSTEM CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY | | AIR. | | | | 3) PROVIDE COMPLETE ENGINEERING AND THE WIND DESIGN | | CRITERIA FOR INSTALLATION OF THE RTU. PLEASE INCLUDE | | ANCHORING DETAILS FOR ATTACHING THE CURB TO THE ROOF | | STRUCTURE AND THE RTU TO THE CURB. | | | | 4) SUBMIT THE NOA FOR THE LOUVERS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|