2017-05-30 17:19:331ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051057
 5/30/17
  
 RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGYGAUGE SUMMIT@FLA/COM-2010, FORM
 506-2010 IS OUTDATED. PLEASE SUBMIT TWO COPIES OF THE
 FLA/COM-2015 VERSION WITH THE CERTIFICATIONS AND
 MANDATORY REQUIREMENTS CHECKLISTS COMPLETED.
  
 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR
 SYSTEM OF RTU-1, UNLESS MANUFACTURER'S DATA INDICATES
 THAT THE SYSTEM CANNOT PRODUCE OVER 2000 CFMS OF SUPPLY
 AIR.
  
 3) PROVIDE COMPLETE ENGINEERING AND THE WIND DESIGN
 CRITERIA FOR INSTALLATION OF THE RTU. PLEASE INCLUDE
 ANCHORING DETAILS FOR ATTACHING THE CURB TO THE ROOF
 STRUCTURE AND THE RTU TO THE CURB.
  
 4) SUBMIT THE NOA FOR THE LOUVERS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER