2017-05-31 15:06:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17051057
 ADD: 4300 MILLER AVE.
 CONT: CANO INC.
 TEL:561-543-1290
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 31/ 2017
 ACTION: DENIED
  
 BUILDING # 3/ OFFICE.
  
 1) PLEASE NOTE THE OWNER OF 4300 MILLER AVE. WILL NEED
 TO SIGN THE PERMIT APPLICATION. THE PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE LIST TC & MARILYN
 DALESSANDRO AS THE OWNERS. 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
 105.1 PERMIT REQUIRED.
  
 2)PLEASE PROVIDE A SURVEY FOR THIS LOT IT APPEARS THE
 BUILDING IS CLOSER THAN 3 FEET TO THE PROPERTY LINE. IT
 APPEARS THE BUILDING MAYBE ON THE PROPERTY LINE SEE
 PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE MAP. THE
 EXTERIOR WALL ADJACENT TO THE PROPERTY LINE WILL NEED
 TO SHOW COMPLIANCE WITH 2014 FBC-B TABLE 602, 1 HOUR
 FIRE RATING.
  
 3) SHEET A-103 SHOWS (3) STACKED WASHER AND DRYERS.
 PLEASE SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE:
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 4) SHEET A403 DETAIL # 6 IS FOR THE ACCESSIBLE RESTROOM
 PLEASE SHOW COMPLIANCE WITH;
 4A) DETAIL # 6 DOES NOT SHOW THE GRAB BARS AT THE WATER
 CLOSET.
 REAR WALL 604.5.2. ACCESS. CODE.
 SIDE WALL 604.5.1. SIDE WALL.
  
 4B) DETAIL # 6 NOTE R10 INDICATES THE INSTALLATION OF A
 18X36 INCH MIRROR/ S/S FRAME, THE BOTTOM OF THE FRAME
 40 INCHES AFF MAXIMUM. 2014 FBC-ACCESS. CODE 603.3
 MIRRORS REQUIRES THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR.
  
 5) SHEET A103 THE FLOOR PLAN DOES NOT INDICATE IF THE 2
 ENTRIES INTO THE BUILDING ARE LEVEL WITH THE EXTERIOR
 OF THE BUILDING AND COMPLYING WITH 2014 FBC-ACCESS.
 CODE 402.2 COMPONENTS. ACCESSIBLE ROUTES SHALL CONSIST
 OF ONE OR MORE OF THE FOLLOWING COMPONENTS: WALKING
 SURFACES WITH A RUNNING SLOPE NOT STEEPER THAN 1:20,
 DOORWAYS, RAMPS, CURB RAMPS EXCLUDING THE FLARED SIDES,
 ELEVATORS, AND PLATFORM LIFTS. ALL COMPONENTS OF AN
 ACCESSIBLE ROUTE SHALL COMPLY WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTER 4 AND 208.3.1.
  
 6) PLEASE SUBMIT A SITE PLAN AND SHOW COMPLIANCE WITH
 AN ACCESSIBLE PARKING SPACE AND ACCESS AISLE WHERE THE
 OCCUPANT WILL BE ABLE TO TRAVEL FROM THE VEHICLE TO THE
 FRONT ENTRY. ACCESS. CODE 502.2 VEHICLE SPACES. EACH
 PARKING SPACE MUST BE AT LEAST 12 FEET (3658 MM) WIDE,
 SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL HAVE AN
 ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
  
 7) SHEET A-501 DETAIL # 9 NEW CURB AT EXISTING ROOF.
 THIS APPEARS TO BE A NEW ROOF TOP OPENING THAT WILL BE
 CUT INTO THE CONCRETE ROOF DECK. THERE IS NO DETAILS AS
 TO REQUIRED REINFORCEMENT NOR LOCATION IN REGARDS TO
 THE CONCRETE JOIST. THE DETAIL WILL ALSO NEED TO
 PROVIDE A WIND ANALYSIS FOR THE ANCHORING OF THE CURB
 TO THE ROOF DECK AS WELL AS THE RTU TO THE CURB. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved