2017-05-26 14:17:58BUILDING PLAN REVIEW
 NORTON MUSEUM
 W. P. B. SUBMITTAL: 17051037 ROOFING SUBMITTALS
 W. P. B. PERMIT: 16050912 BUILDING PERMIT
 ADD: 1451 S. OLIVE AVE.
 CONT: GILBANE
 TEL: 561-236-7052
 E-MAIL: [email protected] MICHAEL IZZO
 E-MAIL: [email protected] MICHAEL J BEAUMIER
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: FRI. MAY 26/ 2017
 ACTION: DENIED
  
 1) PLEASE NOTE OF THE DIFFERENT ROOFING SUBMITTALS NO
 ROOFING PRODUCT APPROVALS WAS SUBMITTED FOR ANY OF THE
 PRODUCTS SUBMITTED.
 2014 FBC-B , 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 2) SUBMITTAL CROWTHER UNDERLAYMENT POLYGLASS MTS 60 MIL
 UNDERLAYMENT WAS NOT APPROVED / RESUBMIT. WHY SUBMITTED
 TO THE BUILDING DEPARTMENT WHEN NOT APPROVED. FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS
 ETC..
  
 3) FOR EACH OF THE ROOFING PRODUCT APPROVALS PLEASE
 IDENTIFY THE TYPE OF ROOF DECK , ROOF TOP INSULATION,
 IF ENHANCED FASTENING IS REQUIRED, IF THE PRODUCT
 APPROVAL REQUIRES ENGINEERING FOR THE ENHANCED
 FASTENING SCHEDULE. SEE LIMITATIONS OF THE PRODUCT
 APPROVAL. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER OR REGISTERED
 ARCHITECT.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE
 COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR
 ON SUBSEQUENT REVIEWS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER