2017-05-26 14:17:58 | BUILDING PLAN REVIEW |
| NORTON MUSEUM |
| W. P. B. SUBMITTAL: 17051037 ROOFING SUBMITTALS |
| W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| ADD: 1451 S. OLIVE AVE. |
| CONT: GILBANE |
| TEL: 561-236-7052 |
| E-MAIL: [email protected] MICHAEL IZZO |
| E-MAIL: [email protected] MICHAEL J BEAUMIER |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: FRI. MAY 26/ 2017 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE OF THE DIFFERENT ROOFING SUBMITTALS NO |
| ROOFING PRODUCT APPROVALS WAS SUBMITTED FOR ANY OF THE |
| PRODUCTS SUBMITTED. |
| 2014 FBC-B , 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| VENTILATORS |
| |
| 2) SUBMITTAL CROWTHER UNDERLAYMENT POLYGLASS MTS 60 MIL |
| UNDERLAYMENT WAS NOT APPROVED / RESUBMIT. WHY SUBMITTED |
| TO THE BUILDING DEPARTMENT WHEN NOT APPROVED. FBC |
| 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| ETC.. |
| |
| 3) FOR EACH OF THE ROOFING PRODUCT APPROVALS PLEASE |
| IDENTIFY THE TYPE OF ROOF DECK , ROOF TOP INSULATION, |
| IF ENHANCED FASTENING IS REQUIRED, IF THE PRODUCT |
| APPROVAL REQUIRES ENGINEERING FOR THE ENHANCED |
| FASTENING SCHEDULE. SEE LIMITATIONS OF THE PRODUCT |
| APPROVAL. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| ARCHITECT. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| ON SUBSEQUENT REVIEWS. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |