2017-07-28 14:12:19 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW (2ND REVIEW) COMMENTS: |
| |
| 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY. |
| RISER DIAGRAM IS NOT COMPLETE, DOES NOT SHOW NEW PANEL |
| FOR GUEST HOUSE (WHERE IS THIS FED FROM?), DOES NOT |
| PROVIDE WIRE SIZES AS REQUESTED. PROVIDE AS PREVIOUSLY |
| REQUESTED: "PROVIDE RISER DIAGRAM SHOWING EXISTING |
| SERVICE AND ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND |
| CONDUIT SIZE". NEC 215.5, FBC 107.3.5 |
| 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY. |
| LOAD FOR SERVICE WAS NOT SUPPLIED ON PREVIOUS PERMIT |
| 17050712. PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE |
| LOAD CALCULATION FOR MAIN SERVICE INCLUDING NEW LOADS |
| TO BE ADDED TO DETERMINE CURRENT SERVICE IS |
| SUFFICIENT". NEC 220, FBC RE3602.2 |
| 3. PREVIOUS COMMENT #3 NOT ADDRESSED SATISFACTORILY. |
| RESPONSE TO COMMENT STATES THAT THE SERVICE WILL BE |
| MOUNTED ON GUEST HOUSE WHEN BUILT. SHOW LOCATION OF |
| SERVICE ON PLAN. SHOW LOCATION OF NEW 100 AMP PANEL. BE |
| ADVISED THAT ANY SEPARATE STRUCTURE IS REQUIRED TO HAVE |
| A MAIN BREAKER OR DISCONNECT FOR THAT STRUCTURE. THE |
| RISER DIAGRAM PROVIDED SHOWS THE OTHER PANELS AS MAIN |
| LUG ONLY PANELS, WHICH WILL NEED TO BE CORRECTED. |
| PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE DISCONNECT |
| FOR ELECTRICAL SERVICE TO NEW BUILDING PER SECTION II |
| OF THE NEC". NEC 225.30, 225.31, 225.33 |
| 4. PREVIOUS COMMENT #4 NOT ADDRESSED SATISFACTORILY. |
| EACH SEPARATE BUILDING OR STRUCTURE MUST HAVE A |
| GROUNDING ELECTRODE SYSTEM ESTABLISHED AND BONDED |
| TOGETHER PER NEC 250.32. PROVIDE AS PREVIOUSLY |
| REQUESTED: "PROVIDE GROUNDING ELECTRODE CONDUCTOR AND |
| GROUNDING ELECTRODE AT SEPARATE BUILDING WITH |
| INTERSYSTEM BONDING TERMINATION POINT". NEC 250.32, |
| 250.64, 250.94, FBC RE3609.3.5 |
| 5.PREVIOUS COMMENT #5 ADDRESSED, BUT NEEDS CORRECTION. |
| WATER HEATER IS SHOWN WITH A 30 AMP BREAKER, THIS |
| SHOULD BE A 25 AMP PER CODE(BASED ON 4500 WATTS). |
| BATHROOM OUTLETS REQUIRES A DEDICATED 20 AMP CIRCUIT |
| WITH GFCI PROTECTION(THE RECEPTACLES DO NOT CURRENTLY |
| SHOW GFCI PROTECTION). THE OUTLETS IN THE STORAGE AREA |
| REQUIRE GFCI PROTECTION(THE RECEPTACLES DO NOT |
| CURRENTLY SHOW GFCI PROTECTION).PROVIDE CORRECTION. NEC |
| 210.8, 210.11, 408.4, 422.13; FBC RE3703.4, RE 3902.1, |
| RE3902.2 |
| 6. RISER PROVIDED SHOW 3 LEADS OF 2/0 TO 200 AMP PANEL. |
| 2/0 IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC |
| 310.15(B)(16); FBC RE3602.2 |
| 7. PREVIOUS COMMENT #7 NOT ADDRESSED SATISFACTORILY. |
| RESPONSE STATED THE LIGHT AND FAN LOCATIONS WERE MOVED, |
| HOWEVER, THEY ARE IS THE SAME LOCATION. PROVIDE AS |
| PREVIOUSLY REQUESTED: "IT APPEARS FROM SCALING THE |
| PRINT THAT THERE ARE LIGHT FIXTURES AND CEILING FANS |
| LOCATED WITHIN THE 5 FEET HORIZONTAL AND 12 FEET HEIGHT |
| ZONE DESCRIBED IN NEC 680.22. PROVIDE CORRECTION". NEC |
| 680.22(B), FBC RE4203.4 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |