2017-07-28 14:12:19CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW (2ND REVIEW) COMMENTS:
  
 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY.
 RISER DIAGRAM IS NOT COMPLETE, DOES NOT SHOW NEW PANEL
 FOR GUEST HOUSE (WHERE IS THIS FED FROM?), DOES NOT
 PROVIDE WIRE SIZES AS REQUESTED. PROVIDE AS PREVIOUSLY
 REQUESTED: "PROVIDE RISER DIAGRAM SHOWING EXISTING
 SERVICE AND ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND
 CONDUIT SIZE". NEC 215.5, FBC 107.3.5
 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY.
 LOAD FOR SERVICE WAS NOT SUPPLIED ON PREVIOUS PERMIT
 17050712. PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE
 LOAD CALCULATION FOR MAIN SERVICE INCLUDING NEW LOADS
 TO BE ADDED TO DETERMINE CURRENT SERVICE IS
 SUFFICIENT". NEC 220, FBC RE3602.2
 3. PREVIOUS COMMENT #3 NOT ADDRESSED SATISFACTORILY.
 RESPONSE TO COMMENT STATES THAT THE SERVICE WILL BE
 MOUNTED ON GUEST HOUSE WHEN BUILT. SHOW LOCATION OF
 SERVICE ON PLAN. SHOW LOCATION OF NEW 100 AMP PANEL. BE
 ADVISED THAT ANY SEPARATE STRUCTURE IS REQUIRED TO HAVE
 A MAIN BREAKER OR DISCONNECT FOR THAT STRUCTURE. THE
 RISER DIAGRAM PROVIDED SHOWS THE OTHER PANELS AS MAIN
 LUG ONLY PANELS, WHICH WILL NEED TO BE CORRECTED.
 PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE DISCONNECT
 FOR ELECTRICAL SERVICE TO NEW BUILDING PER SECTION II
 OF THE NEC". NEC 225.30, 225.31, 225.33
 4. PREVIOUS COMMENT #4 NOT ADDRESSED SATISFACTORILY.
 EACH SEPARATE BUILDING OR STRUCTURE MUST HAVE A
 GROUNDING ELECTRODE SYSTEM ESTABLISHED AND BONDED
 TOGETHER PER NEC 250.32. PROVIDE AS PREVIOUSLY
 REQUESTED: "PROVIDE GROUNDING ELECTRODE CONDUCTOR AND
 GROUNDING ELECTRODE AT SEPARATE BUILDING WITH
 INTERSYSTEM BONDING TERMINATION POINT". NEC 250.32,
 250.64, 250.94, FBC RE3609.3.5
 5.PREVIOUS COMMENT #5 ADDRESSED, BUT NEEDS CORRECTION.
 WATER HEATER IS SHOWN WITH A 30 AMP BREAKER, THIS
 SHOULD BE A 25 AMP PER CODE(BASED ON 4500 WATTS).
 BATHROOM OUTLETS REQUIRES A DEDICATED 20 AMP CIRCUIT
 WITH GFCI PROTECTION(THE RECEPTACLES DO NOT CURRENTLY
 SHOW GFCI PROTECTION). THE OUTLETS IN THE STORAGE AREA
 REQUIRE GFCI PROTECTION(THE RECEPTACLES DO NOT
 CURRENTLY SHOW GFCI PROTECTION).PROVIDE CORRECTION. NEC
 210.8, 210.11, 408.4, 422.13; FBC RE3703.4, RE 3902.1,
 RE3902.2
 6. RISER PROVIDED SHOW 3 LEADS OF 2/0 TO 200 AMP PANEL.
 2/0 IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE3602.2
 7. PREVIOUS COMMENT #7 NOT ADDRESSED SATISFACTORILY.
 RESPONSE STATED THE LIGHT AND FAN LOCATIONS WERE MOVED,
 HOWEVER, THEY ARE IS THE SAME LOCATION. PROVIDE AS
 PREVIOUSLY REQUESTED: "IT APPEARS FROM SCALING THE
 PRINT THAT THERE ARE LIGHT FIXTURES AND CEILING FANS
 LOCATED WITHIN THE 5 FEET HORIZONTAL AND 12 FEET HEIGHT
 ZONE DESCRIBED IN NEC 680.22. PROVIDE CORRECTION". NEC
 680.22(B), FBC RE4203.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER