Date Text
2017-06-12 13:58:471ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DIMENSIONS FOR THE SHOWERS TO COMPLY
 WITH FBC RES P2708.1
  
 2. PROVIDE DIMENSIONS FOR BATHROOMS TO SHOW COMPLIANCE
 WITH FBC RES P2705.1 5. WATER CLOSETS, LAVATORIES AND
 BIDETS. A WATER CLOSET, LAVATORY OR BIDET SHALL NOT BE
 SET CLOSER THAN 15 INCHES (381 MM) FROM ITS CENTER TO
 ANY SIDE WALL, PARTITION OR VANITY OR CLOSER THAN 30
 INCHES (762 MM) CENTER-TO-CENTER BETWEEN ADJACENT
 FIXTURES. THERE SHALL BE A CLEARANCE OF NOT LESS THAN
 21 INCHES (533 MM) IN FRONT OF A WATER CLOSET, LAVATORY
 OR BIDET TO ANY WALL, FIXTURE OR DOOR.
  
 3. PLEASE SHOW LOCATION OF THE WATER HEATER PER WPB
 AMEND TO FBC 107.2.1
  
 4. A CLEANOUT IS REQUIRED AT THE BASE OF THE SOIL
 STACK. FBC RES P3005.2.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  