Plan Review Notes For Permit 17050988 |
Permit Number |
17050988 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-06-15 15:05:12 | PLAN DENIED | | 1) PROVIDE EQUIPMENT SCHEDULE ON PLANS. | | PER SECTION 107 FBC. | | 2) SHOW LOCATION OF CONDENSER ON PLAN. | | PER SECTION 107 FBC. | | 3) SHOW ACCESS TO AIR HANDLER ON THE PLAN. | | PER SECTION R403.2.4 AIR HANDLING UNITS | | FLORIDA ENERGY CODE 2014 | | 4) PROVIDE A SIGNATURE AND LICENSE NUMBER | | ON THE PLAN ( ON WHO EVER DREW THE PLAN ) | | 5) REFER TO SECTION R 403.2.1 INSULATION. SUPPLY | | DUCT IN ATTIC SHALL BE INSULATED TO A MINIMUM OF R-8 | | FLORIDA ENERGY CODE 2014. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|