Plan Review Notes
Plan Review Notes For Permit 17050971
Permit Number 17050971
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-24 13:06:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE SUBMITTED PLANS SHOW ONLY ON DEVICE ON THE
 FLOOR PLAN; HOWEVER, THERE WERE NUMEROUS DEVICES
 LOCATED ON THE VOLTAGE DROP AND BATTERY CALCULATION
 SHEET.
  
 PLEASE CLARIFY AND/OR CORRECT.
  
  
  
 2) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO
 DETERMINE COMPLAINCE WITH APPLICABLE CODE.
  
 PLEASE PROVIDE THE LOCATION AND TYPE OF EACH PIECE OF
 INSTALLED EQUIPMENT ON THE FLOOR PLAN AND ENSURE THAT
 THEY COMPLY WITH NFPA 72.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  