Plan Review Notes
Plan Review Notes For Permit 17050881
Permit Number 17050881
Review Stop B
Sequence Number 3
Notes
Date Text
2017-07-20 11:17:182014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17050881
 ADD: 805 19TH ST.
 CONT: M. J. EBERSBACH CONSTRUCTION
 TEL: 561-271-0136
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. JULY 20/ 2017
 ACTION: DENIED
  
 1) BUILDING PROVISO: CHANGE OUT OF ALL WINDOWS FOR 1ST
 & 2ND FLOOR. EXCEPTION TO SECTION 704.1 OF THE 2014
 EXISTING BUILDING CODE AN ALLOWABLE 5 PERCENT REDUCTION
 IN THE CLEAR OPENING DIMENSIONS OF THE REPLACEMENT
 WINDOW. THE CONTRACTOR HAS SUBMITTED PICTURES OF
 EXISTING SINGLE HUNG WINDOWS IN THE EXISTING OPENING.
  
 2) 2ND REQUEST. 107.2.4 EXTERIOR WALL ENVELOPE. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURERS
 INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING
 DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING
 DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS
 MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL
 ENVELOPE.
  
 3-4) COMPLIED.
  
 5) NEW COMMENT. SHEET # 2 SHOWS NEW AIR CONDENSERS ON
 CONCRETE PADS PLEASE PROVIDE ENGINEERING HOW THESE
 UNITS WILL BE ANCHORED TO THE CONCRETE PAD. PROVIDE
 LATERAL FORCE RESISTING SYSTEM. 2014 FBC-B 1604.4
 ANALYSIS. SEE MECH. PLAN REVIEW AS WELL.
  
 6) NEW COMMENT. SUBMITTED DOOR AND MULLION PRODUCT
 APPROVAL WITH THE DESIGNER OF RECORD REVIEW. THIS
 REVIEW I COULD FIND NO WINDOW PRODUCT APPROVAL FOR ANY
 TYPE OF WINDOW. THE WINDOW SCHEDULE ON SHEET A.2 DOES
 INDICATE ALL OF THE NEW WINDOWS ARE TO BE SINGLE HUNG
 WINDOWS. PLEASE COMPLY WITH 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(B) WINDOWS.
  
 E-MAIL SENT 07/20/17 11:34 THERE MAYBE OTHER ISSUES
 THAT DEAL WITH THE REQUIRED FLOOR UNDELAYMENT SOUND
 REQUIREMENTS FOR THE 2ND FLOOR.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
  