Plan Review Notes
Plan Review Notes For Permit 17050881
Permit Number 17050881
Review Stop P
Sequence Number 2
Notes
Date Text
2017-07-14 18:29:022ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/24/17
  
 NOT COMPLIED 2ND REQUEST1. SANITARY RISER IS NOT CODE
 COMPLIANT EACH FIXTURE BRANCH SHALL CONNECT TO A WET
 VENT OR BE SEPARATELY VENTED THEY CAN NOT CONNECT
 DIRECTLY TO THE BUILDING DRAIN OR SOIL STACK WITHOUT
 BEING VENTED. PER FBC PL 901.2.1
  
  
  
 TO EXPEDITE PLUMBING APPROVAL I SUGGEST A MEETING BE
 SCHEDULED TO GO OVER SANITARY RISER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711