Plan Review Notes
Plan Review Notes For Permit 17050881
Permit Number 17050881
Review Stop M
Sequence Number 2
Notes
Date Text
2017-07-14 11:49:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17050881
 7/14/17
  
 RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS: 1)
 REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. IF USING NATURAL
 VENTILATION SEE SECTION 402.1.
  
 2) COMMENT #3 FROM THE 1ST REVIEW STILL PARTIALLY
 EXISTS: SUBMIT AHRI CERTIFICATES FOR THE NEW AC
 SYSTEMS.
  
 3) COMMENT #4 FROM THE 1ST REVIEW STILL PARTIALLY
 EXISTS: PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSERS- SECTION 301.15.
  
 4) NEW COMMENT: CLARIFY HOW AIR IS BEING RETURNED FROM
 EACH BEDROOM #2- SEE SECTION 601.5
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  