2017-05-24 17:12:511ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/24/17
  
 1. SANITARY RISER IS NOT CODE COMPLIANT EACH FIXTURE
 BRANCH SHALL CONNECT TO A WET VENT OR BE SEPARATELY
 VENTED THEY CAN NOT CONNECT DIRECTLY TO THE BUILDING
 DRAIN OR SOIL STACK WITHOUT BEING VENTED. PER FBC PL
 901.2.1
  
 2. PROVIDE LOCATION OF NEW TANKLESS HEATER. PER WPB
 AMEND TO FBC 107.2.1
  
 3. PROVIDE MANUFACTURE SPECS FOR TANKLESS HEATER. PER
 WPB AMEND TO FBC 107.2.1
  
 TO EXPEDITE PLUMBING APPROVAL I SUGGEST A MEETING BE
 SCHEDULED TO GO OVER SANITARY RISER.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  