Plan Review Notes For Permit 17050881 |
Permit Number |
17050881 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-25 17:07:45 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17050881 | | 5/25/17 | | | | RESULTS: DENIED. | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW MINI-SPLIT SYSTEMS IN ACCORDANCE WITH SECTION | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | 3) PROVIDE AC EQUIPMENT SCHEDULES ON THE PLAN, AND | | SUBMIT AHRI CERTIFICATES FOR EACH SYSTEM. | | | | 4) SHOW THE LOCATIONS OF THE EXTERIOR CONDENSER UNITS | | AND PROVIDE ENGINEERED INSTALLATION DETAILS- SECTION | | 301.15 | | | | 5) THE PALM BEACH COUNTY APPRAISOR'S REPORT SHOWS NO | | HEATING OR COOLING IN THE APARTMENTS, HOWEVER NOW THAT | | NEW AC SYSTEMS ARE BEING INSTALLED, THE BUILDING SHALL | | BE COMPLIANCE WITH THE CURRENT FBC-14 ENERGY | | CONSERVATION CODE. PLEASE REFER TO SECTION R101.4.5 AND | | SUBMIT DOCUMENTATION OF ENEGY EFFICIENCY COMPLIANCE | | USING EITHER THE PRESCIPTIVE OR PERFORMANCE BASED | | | | METHOD- SEE SECTION R101.5.1 FOR COMPLIANCE MATERIALS | | INFORMATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|