2017-06-01 08:11:43CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 1ST REVIEW:
 1. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND
 VALUE OF WORK. FBC 105.1 , 109.3
 2. SHEET 4.0 STATES THAT THE ELECTRICAL LOAD
 CALCULATION WAS PROVIDED UNDER PERMIT #17030423. IN
 RESEARCHING THIS PERMIT, I FOUND THE LOAD CALCULATIOIN
 TO BE INCOMPLETE, WITH NO LOAD LISTED FOR HOUSE PANEL.
 ADDITIONALLY, THE ADDITION OF TANKLESS WATER HEATERS IN
 EACH UNIT WILL INCREASE THE LOAD. THEREFORE, PROVIDE
 COMPLETE LOAD CALCULATION FOR BUILDING WITH ALL LOADS
 LISTED TO JUSTIFY SIZING OF SERVICE. SPECIFY METHOD
 USED FOR CALCULATION. NEC 220, FBC R E3602.2
 3. THE 2 SMALL APPLIANCE CIRCUITS FOR THE KITCHEN SHALL
 HAVE NO OTHER OUTLETS. THE BATHROOM CAN NOT BE SUPPLIED
 FROM ONE OF THESE CIRCUITS. PROVIDE CORRECTION. NEC
 210.52(B)(2), 210.11(C)(3), FBC R E3703.2, E3901.3.1
 4. THERE IS A CONFLICT WITH THE PANEL SCHEDULE AND WHAT
 IS SHOWN ON PLAN IN REFERENCE TO THE A/C SYSTEM. PANEL
 SCHEDULE SHOWS AN A/C AND AHU, PLAN SHOWS A MINI-SPLIT
 SYSTEM. PROVIDE CORRECTION AND INCLUDE IN ABOVE
 MENTIONED LOAD CALCULATION. FBC 107.2.1, FBC R E3602.2
 5. PROVIDE FLOOR PLAN FOR EACH UNIT. FBC 107.2.1
 6. PENINSUAL IN KITCHEN REQUIRES AN OUTLET, SHOW ON
 PLAN. NEC 210.52(C)(3), FBC R E3901.4.3
 7. PROVIDE PANEL SCHEDULE FOR HOUSE PANEL. NEC 408.4
 8. PROVIDE CLARIFICATION FOR WIRING TO RANGE AND
 TANKLESS WATER HEATER. #8 ROMEX, WHICH IS TYPICAL IN
 HOUSE WIRING, IS NOT RATED FOR THE 50 AMP BREAKER SHOWN
 IN PANEL SCHEDULE. NEC 334.80, FBC R E3705.4.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  