2017-06-01 08:11:43 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| 1ST REVIEW: |
| 1. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND |
| VALUE OF WORK. FBC 105.1 , 109.3 |
| 2. SHEET 4.0 STATES THAT THE ELECTRICAL LOAD |
| CALCULATION WAS PROVIDED UNDER PERMIT #17030423. IN |
| RESEARCHING THIS PERMIT, I FOUND THE LOAD CALCULATIOIN |
| TO BE INCOMPLETE, WITH NO LOAD LISTED FOR HOUSE PANEL. |
| ADDITIONALLY, THE ADDITION OF TANKLESS WATER HEATERS IN |
| EACH UNIT WILL INCREASE THE LOAD. THEREFORE, PROVIDE |
| COMPLETE LOAD CALCULATION FOR BUILDING WITH ALL LOADS |
| LISTED TO JUSTIFY SIZING OF SERVICE. SPECIFY METHOD |
| USED FOR CALCULATION. NEC 220, FBC R E3602.2 |
| 3. THE 2 SMALL APPLIANCE CIRCUITS FOR THE KITCHEN SHALL |
| HAVE NO OTHER OUTLETS. THE BATHROOM CAN NOT BE SUPPLIED |
| FROM ONE OF THESE CIRCUITS. PROVIDE CORRECTION. NEC |
| 210.52(B)(2), 210.11(C)(3), FBC R E3703.2, E3901.3.1 |
| 4. THERE IS A CONFLICT WITH THE PANEL SCHEDULE AND WHAT |
| IS SHOWN ON PLAN IN REFERENCE TO THE A/C SYSTEM. PANEL |
| SCHEDULE SHOWS AN A/C AND AHU, PLAN SHOWS A MINI-SPLIT |
| SYSTEM. PROVIDE CORRECTION AND INCLUDE IN ABOVE |
| MENTIONED LOAD CALCULATION. FBC 107.2.1, FBC R E3602.2 |
| 5. PROVIDE FLOOR PLAN FOR EACH UNIT. FBC 107.2.1 |
| 6. PENINSUAL IN KITCHEN REQUIRES AN OUTLET, SHOW ON |
| PLAN. NEC 210.52(C)(3), FBC R E3901.4.3 |
| 7. PROVIDE PANEL SCHEDULE FOR HOUSE PANEL. NEC 408.4 |
| 8. PROVIDE CLARIFICATION FOR WIRING TO RANGE AND |
| TANKLESS WATER HEATER. #8 ROMEX, WHICH IS TYPICAL IN |
| HOUSE WIRING, IS NOT RATED FOR THE 50 AMP BREAKER SHOWN |
| IN PANEL SCHEDULE. NEC 334.80, FBC R E3705.4.4 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |