Notes |
Date |
Text |
2017-06-06 06:18:28 | 1) INDICATE THE SIZE OF THE DEVICE BEING INSTALLED ON | | THE SPECIFICATIONS AND ON THE PERMIT APPLICATION. WPB | | AMEND. TO FBC SEC.107.2.1. 2ND REQUEST. | | 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE PER NSF 61 | | AND THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL. | | THE SUBMITTED SPECIFICATIONS DO NOT SHOW THE DEVICE IS | | LEAD FREE. 2ND REQUEST. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|