Plan Review Notes
Plan Review Notes For Permit 17050847
Permit Number 17050847
Review Stop P
Sequence Number 2
Notes
Date Text
2017-06-06 06:18:281) INDICATE THE SIZE OF THE DEVICE BEING INSTALLED ON
 THE SPECIFICATIONS AND ON THE PERMIT APPLICATION. WPB
 AMEND. TO FBC SEC.107.2.1. 2ND REQUEST.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE PER NSF 61
 AND THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
 THE SUBMITTED SPECIFICATIONS DO NOT SHOW THE DEVICE IS
 LEAD FREE. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved