Plan Review Notes
Plan Review Notes For Permit 17050847
Permit Number 17050847
Review Stop P
Sequence Number 1
Notes
Date Text
2017-05-19 09:02:541) INDICATE THE SIZE OF THE DEVICE BEING INSTALLED ON
 THE SPECIFICATIONS AND ON THE PERMIT APPLICATION. WPB
 AMEND. TO FBC SEC.107.2.1.
 2) ALL BACKFLOW DEVICES MUST BE LEAD FREE PER NSF 61
 AND THE CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
 THE SUBMITTED SPECIFICATIONS DO NOT SHOW THE DEVICE IS
 LEAD FREE AND IT IS NOT LISTED AS LEAD FREE ON THE USC
 WEBSITE. ALL BACKFLOW DEVICES MUST BE ON THE UNIVERSITY
 OF SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED
 DEVICES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW