2017-06-15 13:01:56 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. ORIGINAL SUBMITTAL PROPOSED USING WHISPER PAD AS AN |
| UNDERLAYMENT. |
| 2. RE-SUBMITTAL CONSISTS OF TWO DIFFERENT UNDERLAYMENTS |
| (0264070 LVT UNDERLAYMENT AND UNDERLAYMENT NO. |
| 120110.L004T). |
| 3. PROVIDE TEST REPORTS FOR THE THREE ASTM'S (E-84, |
| E-90 & E-492) FOR ONE UNDERLAYMENT TESTED ON THE |
| EXISTING 6 IN. CONCRETE SLAB-FLOOR ASSEMBLY. |
| |
| FBC 603.1 FLAME SPREAD ? ASTM E-84 |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| |
| |
| |