2017-06-15 13:01:56BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ORIGINAL SUBMITTAL PROPOSED USING WHISPER PAD AS AN
 UNDERLAYMENT.
 2. RE-SUBMITTAL CONSISTS OF TWO DIFFERENT UNDERLAYMENTS
 (0264070 LVT UNDERLAYMENT AND UNDERLAYMENT NO.
 120110.L004T).
 3. PROVIDE TEST REPORTS FOR THE THREE ASTM'S (E-84,
 E-90 & E-492) FOR ONE UNDERLAYMENT TESTED ON THE
 EXISTING 6 IN. CONCRETE SLAB-FLOOR ASSEMBLY.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
  
  