Date Text
2017-05-30 16:57:14FAILED
  
 1) SHEET M1.1 SHOWS CONDENSING UNITS ON THE GROUND
 LEVEL. PROVIDE THE SITE PLAN SHOWING WHERE THESE UNITS
 AND THE PAD ARE LOCATED IN RELATIONSHIP TO THE BUILDING
 AND DRIVEWAY CURB (INCLUDE DIMENSIONS).
  
 2) SHEETS PS1.1, PLUMBING SITE PLAN, AND ES1.1,
 ELECTRIC SITE PLAN DO NOT SHOW THE ACCURATE SITE PLAN
 FOR THE NEW GENERATOR, ATS AND TRANSFORMER LOCATIONS.
 THE GAS RISER AND THE FPL LINES SHALL BE CLEARLY SHOWN
 OUTSIDE OF THE REQUIRED EIGHT (8) FOOT LANDSCAPE
 BUFFER.
  