Notes |
Date |
Text |
2017-05-30 16:57:14 | FAILED | | | | 1) SHEET M1.1 SHOWS CONDENSING UNITS ON THE GROUND | | LEVEL. PROVIDE THE SITE PLAN SHOWING WHERE THESE UNITS | | AND THE PAD ARE LOCATED IN RELATIONSHIP TO THE BUILDING | | AND DRIVEWAY CURB (INCLUDE DIMENSIONS). | | | | 2) SHEETS PS1.1, PLUMBING SITE PLAN, AND ES1.1, | | ELECTRIC SITE PLAN DO NOT SHOW THE ACCURATE SITE PLAN | | FOR THE NEW GENERATOR, ATS AND TRANSFORMER LOCATIONS. | | THE GAS RISER AND THE FPL LINES SHALL BE CLEARLY SHOWN | | OUTSIDE OF THE REQUIRED EIGHT (8) FOOT LANDSCAPE | | BUFFER. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] |
|