Date |
Text |
2017-06-06 12:05:18 | 1ST REVIEW: FBC 2014 5TH EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. C-4 DETAIL 1/C4 THE LAYOUT DOES NOT MATCH THE |
| REST OF THE PLAN AND DOES NOT SHOW THE REQUIRED |
| LAVATORY IN ACCESSIBLE STALL PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 2. PROVIDE THE DIMENSIONS FOR THE ACCESSIBLE BATHROOM |
| STALL. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| RIGHT-HAND APPROACH. |
| |
| 4. SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE WALL. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| FROM THE REAR WALL. |
| 604.5.2 REAR WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| |
| 5. SHOW COMPLIANCE WITH FBC ACC 606.2 CLEAR FLOOR |
| SPACE. |
| A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 6. SHOW COMPLIANCE WITH FBC ACC 602.4 SPOUT HEIGHT. |
| SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. |
| 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. |
| SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| 602.2 CLEAR FLOOR SPACE. |
| UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 7. THE BREAKROOM SINK SHALL COMPLY WITH FBC ACC 606.2 |
| CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 8. A BACK FLOW DEVICE IS REQUIRED ON THE REFRIGERATOR |
| ICE MACHINE. PER FBC PL 608.3 |
| |
| 9. FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| 10. C2 MIXING VALVE IS NOT SHOWN ON WATER RISER DIAGRAM |
| OR FLAT PLAN PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |