2017-06-06 12:05:181ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. C-4 DETAIL 1/C4 THE LAYOUT DOES NOT MATCH THE
 REST OF THE PLAN AND DOES NOT SHOW THE REQUIRED
 LAVATORY IN ACCESSIBLE STALL PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PROVIDE THE DIMENSIONS FOR THE ACCESSIBLE BATHROOM
 STALL. PER WPB AMEND TO FBC 107.2.1
  
 3. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH.
  
 4. SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 5. SHOW COMPLIANCE WITH FBC ACC 606.2 CLEAR FLOOR
 SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6. SHOW COMPLIANCE WITH FBC ACC 602.4 SPOUT HEIGHT.
 SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 7. THE BREAKROOM SINK SHALL COMPLY WITH FBC ACC 606.2
 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8. A BACK FLOW DEVICE IS REQUIRED ON THE REFRIGERATOR
 ICE MACHINE. PER FBC PL 608.3
  
 9. FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 10. C2 MIXING VALVE IS NOT SHOWN ON WATER RISER DIAGRAM
 OR FLAT PLAN PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  