2017-05-30 15:21:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050836
 5/20/17
  
 RESULTS: DENIED.
  
 1) THE $65,000.00 VALUE LISTED ON THE PERMIT
 APPLICATION APPEARS VERY LOW FOR THE SCOPE OF THE
 PROPOSED PROJECT. PLEASE SEE SECTION 109.3 FBC-
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES,
  
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. PLEASE
 NOTE THAT THE VALUE FOR MECHANICAL SHALL INCLUDE THE
 LABOR,
  
 MATERIALS, AND EQUIPMENT FOR BOTH TENANT SPACES AS
 SHOWN ON THE PLANS.
  
 2) C-7: IN ADDITION TO THE ROOF HATCH FOR THE HOME
 GOODS OCCUPANCY, A ROOF HATCH AND PERMANENT LADDER IS
 REQUIRED FOR THE ADJACENT TENANT. PLEASE SHOW THE
 LOCATION OF THE HATCH AND PROVIDE PERMANENT LADDER
 DETAILS FOR ACCESS TO BOTH ROOFS IN ACCORDANCE WTH
 SECTIOON 306.4.
  
 3) M-1: A THOROUGH REVIEW OF THE AC AND ENERGY
 CALCULATIONS CANNOT BE PERFORMED WITHOUT O/A
 CALCULATIONS AND EQUIPMENT SCHEDULES FOR RTU'S 1, 3 &
 5. PLEASE PROVIDE THE CALCULATIONS AND SCHEDULES ON THE
 PLANS.
  
 4) M-1: THE HEATING COIL SIZING CALCULATIONS FOR RTU'S
 2, 4, 8, 9, & 10 INDICATE THAT 18 KW HEATERS SELECTED
 ARE OVERSIZED.
  
 5) M-1: THE EFFICIENCY RATINGS LISTED IN THE ENERGY
 CALCS FOR RTU'S 2, 4, 8, 9 & 10 ARE HIGHER THAN THE
 RATINGS IN THE SCHEDULE.
  
 6) M-2: DUCT SMOKE DETECTORS ARE REQUIRED FOR ALL RTU
 SYSTEMS SHOWN ON THE PLANS INCLUDING RTU'S 1, 3, 5, 6 &
 7. PROVIDE SYMBOLS ON THE PLANS TO SHOW THEIR
 LOCATIONS. PLEASE NOTE THAT THE REQUIREMENT FOR THE 5.0
 TON SYSTEMS CAN BE WAIVED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE SYSTEMS ARE NOT CAPABLE OF
 PRODUCING OVER 2000 CFMS OF SUPPLY AIR- SECTION
 606.2.1.
  
 7) M-4: PROVIDE COMPLERE ENGINEERING AND THE WIND LOAD
 DESIGN CRITERIA FOR INSTALLATION OF THE NEW AND
 REPLACED RTU'S- SECTION 301.15.
  