2017-06-05 12:54:55 | PERMIT # 17050836 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| 1) REVIEW AND RESPOND TO BUILDING DEPARTMENT COMMENTS. |
| |
| 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED BY EMAIL ([email protected]) |
| ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| 3) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A |
| LOCK/UNLOCK INDICATOR. |
| |
| 4) EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED |
| WITH SIGNS OR STENCILING READING FIRE BARRIER-PROTECT |
| ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| SPACED NOT MORE THAN 15 FEET ON CENTER. |
| |
| 5) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN |
| STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE |
| MAINTAINED AT ALL TIMES. |
| |
| 5) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| BE NEEDED. |
| |
| 6) ALL TENANT SPACES FOR THE MARKETPLACE MUST BE TIED |
| INTO THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH |
| TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION |
| OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE |
| THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A |
| TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE" |
| FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS |
| LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY |
| ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN. |
| SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE |
| PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR |
| "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY |
| REQUIRE THAT THE TENANT FACP BE REMOVED. |
| |
| 7) PER APPROVED MASTER PLANS: MAIN FACP FOR THIS |
| BUILDING IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE |
| DEPARMENT. NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS |
| OF TENANT WHERE TROUBLE IS LOCATED. EACH BUILDING SHALL |
| ALARM/EVACUATE ONLY THE SPACES IN THAT BUILDING (IE AN |
| ALARM IN "B" WILL NOT EVACUATE ANY SPACE IN "A", "BII", |
| OR "C". EACH TENANT SPACE FACP SHALL BE CONNECTED TO |
| MAIN FACP FOR THIS BUILDING VIA MODULES. TENANT SYSTEM |
| SHALL BE COMPATIBLE WITH NOTIFIER OR EQUAL APPROVED |
| MAIN FACP/HARDWARE EACH FLOW/TAMPER SHALL BE ZONED SO |
| THAT AN ALARM WILL SOUND FOR EACH BUILDING SEPARATELY. |
| |
| |
| |