2017-05-23 07:03:43 | 1) SUBMIT TWO COPIES OF CLEAR AND LEGIBLE FLOOR PLANS |
| FOR REVIEW. THE PRINTING ON THE SUBMITTED PLANS IS SO |
| SMALL AND LIGHT IT CANNOT BE READ. WPB AMEND. TO FBC |
| SEC. 107.1, 107.2.1. |
| 2) SUBMIT AN EXISTING FLOOR PLAN SHOWING THE EXISTING |
| CONDITIONS. INDICATE ALL EXISTING ROOMS, FIXTURES, |
| ETC.WPB AMEND. TO FBC SEC. 107.2.1. |
| 3) IS THE ADA TOILET ROOM AN EXISTING ADA TOILET ROOM |
| OR IS IT BEING TRANSFORMED TO A NEW ADA TOILET ROOM? |
| CLEARLY INDICATE SUCH ON THE PLANS. IF NEW, THEN A |
| COMPLETE SET OF PLANS WILL BE REQUIRED SHOWING THE |
| TOILET ROOM DIMENSIONS AND ALL FIXTURE CLEARANCES. |
| 4) SUBMIT A WATER RISER DIAGRAM FOR REVIEW FOR ALL |
| CHANGES TO THE WATER SYSTEM. WPB AMEND. TO FBC SEC. |
| 107.3.5.1.3. |
| 5) THE FLOOR PLAN APPEARS TO NOTE A STEAM OVEN. IF SO, |
| SUBMIT MANUF. SPECS FOR THIS ITEM. |
| 6) INDICATE THE TYPE OF BUSINESS IN THIS SPACE. CITY |
| RECORDS SHOW THIS CURRENTLY AS A THRIFT STORE. THIS |
| COULD BE A CHANGE OF OCCUPANCY PER 2014 FBC SEC. 302 7 |
| & FBC-EXISTING BUILDING CHAPT. 10. |
| 7) THE WORK ORDER NOTES THAT THE UNDERGROUND SANITARY |
| WILL BE REPLACED BUT THE SANITARY DRAWING DOES NOT SHOW |
| ANY UNDERGROUND SANITARY BEING REPLACED. CLARIFY. |
| 8) TEMPERED WATER IS REQUIRED AT THE NEW LAVATORIES. |
| 2014 FBC SEC.607.1. |
| 9) SUBMIT MANUF. SPECIFICATIONS FOR THE INSTANT WATER |
| HEATERS. WPB AMEND. TO FBC-SEC. 107.2.1. |
| 10) WHAT WILL THE TWO NEW SINKS BE USED FOR? INDICATE |
| ON THE PLANS. |
| 11) INDICATE ON THE PLAN WHAT THE STEAM OVEN WILL BE |
| USED FOR. IF COOKING IS GOING TO BE DONE ON THE |
| PREMISES THEN A GREASE INTERCEPTOR/TRAP MAY BE |
| REQUIRED. 2014 FBC-PLUMBING SEC. 1003.3.1. CLARIFY. |
| 12) THE SUBMITTED PLANS ARE VAGUE AS TO THE NATURE OF |
| THIS BUSINESS. SUBMIT COMPLETE, DETAILED |
| INFORMATION/PLANS AS TO THE ENTIRE SCOPE OF WORK TO BE |
| DONE. WPB AMEND. TO FBC SEC. 107.2.1. |
| 13) THE URINAL SHALL COMPLY WITH 2014FBC-ACCESS. SEC |
| 605. A CLEAR FLOOR SPACE COMPLYING WITH 2014 |
| FBC-ACCESS. SEC. 305 POSITIONED FOR A FORWARD APPROCAH |
| SHALL BE PROVIDED. |
| |