2017-05-24 07:16:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NEW SINGLE HUNG WINDOW FOR OPENING NUMBER 3 DOES
 NOT MEET THE REQUIREMENTS OF FBC R310 FOR EMERGENCY AND
 RESCUE OPENINGS. INDICATE IF THERE IS ANOTHER OPENING
 IN THIS BEDROOM THAT MEETS THE REQUIREMENTS OF R310. IF
 THERE IS NO OTHER CODE COMPLIANT OPENING TO THE
 EXTERIOR IN THE BEDROOM, THEN INDICATE THE EXISTING
 WINDOW'S TYPE AND THE NET CLEAR OPENING SIZE OF IT.
 PROVIDE CALCULATIONS TO SHOW THAT THE NET CLEAR OPENING
 DIMENSIONS OF THE EXISTING WINDOW ARE NOT BEING REDUCED
 BY MORE THAN 5-PERCENT PER FBC EXISTING BUILDING
 SECTION 704.1.
  
 2) INDICATE HOW AND WHERE THE MULLIONS WILL BE
 INSTALLED. FBC 107.2.1
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE IMPACT SLIDING
 GLASS DOOR.