Plan Review Notes For Permit 17050731 |
Permit Number |
17050731 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-18 06:57:30 | 1) SUBMIT 2 CCOPIES OF THE SIZING TABLE USED FOR THE | | SIZING OF THE LOW PRESSURE SIDE OF THED GAS SYSTEM OR | | PLACE A NOTE ON BOTH SETS OF PLANS REFERENCING THE | | TABLE USED. 2014 FBC- FUEL GAS SEC. 402.3. | | 2) INDICATE THE LENGTH, SIZE & TYPE OF PIPE MATERIAL | | FOR THE LOW PRESSURE SIDE CONNECTION TO THE GENERATORS. | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE GENERATORS. GENERATORS SHALL BE | | INSTALLED IN ACCORDANCE WITH NFPA 37 AND SHALL MEET THE | | REQUIREMENTS OF UL 2200. | | 4) THE LP TANK APPEARS AS THOUGH IT MAY BE INSTALLED | | NEAR A DRIVEWAY PER PLANS ON RECORD. IDENTIFY ON THE | | PLAN THE TYPE OF AREA WHERE THE TANK IS BEING INSTALLED | | ( PLANTING/LANDSCAPED AREA). IF THE TANK WILL BE | | INSTALLED WHERE VEHICLES ARE EXPECTED, THE TANK, | | FITTING HOUSING, HOUSING COVER, CONTAINER CONNECTIONS | | AND PIPING PERR NFPA 58 SEC. 6.6.6.1 (B) (C). | | 5) A CORROSION PROTECTION SYSTEM SHALL BE INSTALLED | | PERR NFPA 58 SEC. 6.6.6.1 (I). SUBMIT DETAILS. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 6) THE SUBMITTED DOCUMENT FROM TRINITY CONTAINERS IS | | ILLEGIBLE. SUBMIT A CLEAR AND LEGIBLE DDOCUMENT. WPB | | AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|