Plan Review Notes
Plan Review Notes For Permit 17050723
Permit Number 17050723
Review Stop P
Sequence Number 2
Notes
Date Text
2017-08-23 16:10:372ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 2ND REQUEST1. TWO SETS OF PLANS REQUIRED. PER WPB AMEND
 TO FBC 107.1
  
 2. PLAN IS UNCLEAR IT APPEARS LIKE THERE MAY BE TWO
 FLOOR LEVELS BUT NO DETAILS SOME OF THE NOTES ARE
 UNCLEAR EXISTING LAUNDRY NEW MOP SINK LOCATION. I
 SUGGEST THAT SOMEONE COMES IN AND MEETS WITH ME TO
 CLARIFY THIS PLAN BEFORE RESUBMITTING OTHERWISE I WILL
 NOT BE ABLE TO APPROVE PLANS. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  