Plan Review Notes
Plan Review Notes For Permit 17050723
Permit Number 17050723
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-02 15:02:04CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL 1ST REVIEW COMMENTS:
  
 1. PROVIDE 2 COPIES OF PLAN FOR REVIEW. FBC 107.1
 2. SHOW AFCI PROTECTION PER CODE. ALL 120-VOLT, SINGLE
 PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR
 SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC
 210.12, FBC RE3902.12
 3. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER
 SIZE FOR EACH CIRCUIT TO BE INSTALLED. NEC 215.5, 408.4
 4. PROVIDE SMOKE ALARM FOR BASEMENT LEVEL. FBC
 R314.3(3).
 5. PROVIDE CO ALARM WITHIN 10 FEET OF SLEEPING ROOMS.
 FBC R315.1
 6. PROVIDE LIGHT AT EXTERIOR DOOR TO BASEMENT. FOR
 DWELLING UNITS, ATTACHED GARAGES, AND DETACHED GARAGES
 WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH
 GRADE LEVEL ACCESS. NEC 210.70(A)(2)(B), FBC RE3903.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  