2017-05-30 13:29:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET E 1 - THERE ARE INCORRECT EDITIONS DATES |
| REFERENCES TO THE FIRE CODES INDICATED. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| |
| |
| |
| 2) SHEET E 1 - THIS INSTALLATION APPEARS TO FUNCTION AS |
| THE BACKUP TO THE LIFE SAFETY SYSTEMS. |
| |
| EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| NFPA 110, 2013 EDITION. |
| |
| PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE |
| NOTE. |
| |
| |
| |
| 3) THE SCOPE OF WORK DOES NOT ADDRESS HOW LONG THE |
| INSTALLTION WILL TAKE AND/OR FOR PROVIDING APPLICABLE |
| ASSURANCES OF MAINTAINING THE EXISTING LIFE SAFETY |
| PROTECTION. |
| |
| PLEASE PROVIDE. |
| |
| |
| |
| 4) ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE |
| DONE UNDER SEPARATE SHOP DRAWING BY CERTIFIED LIFE |
| SAFETY CONTRACTORS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE. |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |