2017-05-18 08:50:55 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17041119 |
| W. P. B. PERMIT: 15031312 |
| ADD: 333 FERN ST. |
| CONT: KAST CONSTRUCTION |
| CONTACT :ROB HILL |
| TEL: (561)689-2910 |
| E-MAIL: [email protected] |
| |
| 1) THE BREAK METAL AT ENTRY CLADDING CALCULATIONS |
| SUBMITTAL, THE COVER PAGE SIGNED AND SEALED BY EVAN |
| KENNEDY DOES NOT INCLUDE HOW MANY PAGES ARE COVERED |
| UNDER THIS SEAL. WITHIN THE REPORT ARE MARKED PAGES 1-5 |
| WITH A COPIED AND MINIATURIZED SIGNATURE AND SEAL. |
| |
| 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| 61G15-23.001 ENGINEERS SEALS ACCEPTABLE TO THE BOARD. |
| SAID SEAL SHALL BE A MINIMUM OF 1 7/8 INCHES IN |
| DIAMETER, TO SAY LICENSE NOT CERTIFICATE. ALL ENGINEERS |
| MUST BE UTILIZING SAID SEAL NO LATER THAN JANUARY 1, |
| 2006. |
| |
| 2) WIND CALCULATIONS ARE BASED ON ASCE 7-10 LOW RISE |
| BUILDINGS (H<60 FT.) PLEASE NOTE NEGATIVE PRESSURES ARE |
| TAKEN FROM THE ROOF LEVEL. NEGATIVE PRESSURES(Z), |
| POSITIVE PRESSURES( H). ASCE 7-10. |
| THIS IS A 16 STORY HIGH-RISE. ELEVATION TAKEN @ 15 |
| FEET. CALCULATIONS NOT SHOWN ONLY THE END VALUES. |
| |
| 3) ACM PANELS ARE AVAILABLE IN 3MM, 4MM AND 6MM |
| THICKNESSES IN EITHER A STANDARD POLYETHYLENE (PE) OR |
| FIRE RESISTANT (FR) CORE. NO PRODUCT INFORMATION HAS |
| BEEN SUBMITTED. 2010 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(C) PANEL WALLS: ACM PANELS AND OTHER PRODUCTS |
| INTRODUCED BY NEW TECHNOLOGIES |
| |
| 4) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1407.11.1- |
| 1407.11. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |