2017-05-16 08:19:551ST REVIEW FBC-2014 BUILDING
 REVISION #17050663
 MASTER #17050663
 5/16/17
  
 1ST REVIEW OF THE SUBMITTED ROOF CERTIFICATION LETTER
 FROM UNIVERSAL ENGINEERING.
  
 RESULTS: DENIED
  
 1) PLEASE CLARIFY HOW THE INSPECTIONS OF THE ROOFS WAS
 ACCOMPLISHED. WERE RANDOW SECTIONS OF THE SLOPED AND
 FLAT ROOF COVERINGS REMOVED TO OBSERVE THE UNDELAYMENTS
 AND ROOF SHEATHING NAILING? PLEASE SUBMIT PHOTOS OF ALL
 REMOVED SECTIONS.
  
 2) THE LETTER DOES NOT CERTIFY THAT TWO LAYERS OF
 UNDERLAYMENT WERE INSTALLED WITH A 19 INCH OVERLAP- SEE
 SECTION R905.2.7 FBC-14 RESIDIENTIAL.
  
 3) THE LETTER DOES NOT VERIFY THAT APPROVED ROOFING
 MATERIALS WERE INSTALLED. PLEASE PROVIDE THE FLORIDA
 PRODUCT APPROVAL NUMBER FOR THE FLAT ROOF MATERIALS,
 AND THE MIAMI-DADE NOA NUMBER FOR THE SLOPED ROOFING.
  
 4) THE ENGINEER CAN EITHER PROVIDE HIS CALCULATIONS AND
 REQUIRED ENHANCED FASTENER SPACINGS FOR THE FLAT ROOF
 PERIMETER AND CORNER AREAS, OR SUBMIT THE NOA FOR THE
 CERTAINTEED FLAT ROOF WITH THE SYSTEM, EXPOSURE
 CATEGORY, ROOF HEIGHT, AND ENHANCED NAILING PATTERNS
 CIRCLED OR HIGHLIGHTED ON THE DOCUMENT.
  