Notes |
Date |
Text |
2017-05-16 08:19:55 | 1ST REVIEW FBC-2014 BUILDING | | REVISION #17050663 | | MASTER #17050663 | | 5/16/17 | | | | 1ST REVIEW OF THE SUBMITTED ROOF CERTIFICATION LETTER | | FROM UNIVERSAL ENGINEERING. | | | | RESULTS: DENIED | | | | 1) PLEASE CLARIFY HOW THE INSPECTIONS OF THE ROOFS WAS | | ACCOMPLISHED. WERE RANDOW SECTIONS OF THE SLOPED AND | | FLAT ROOF COVERINGS REMOVED TO OBSERVE THE UNDELAYMENTS | | AND ROOF SHEATHING NAILING? PLEASE SUBMIT PHOTOS OF ALL | | REMOVED SECTIONS. | | | | 2) THE LETTER DOES NOT CERTIFY THAT TWO LAYERS OF | | UNDERLAYMENT WERE INSTALLED WITH A 19 INCH OVERLAP- SEE | | SECTION R905.2.7 FBC-14 RESIDIENTIAL. | | | | 3) THE LETTER DOES NOT VERIFY THAT APPROVED ROOFING | | MATERIALS WERE INSTALLED. PLEASE PROVIDE THE FLORIDA | | PRODUCT APPROVAL NUMBER FOR THE FLAT ROOF MATERIALS, | | AND THE MIAMI-DADE NOA NUMBER FOR THE SLOPED ROOFING. | | | | 4) THE ENGINEER CAN EITHER PROVIDE HIS CALCULATIONS AND | | REQUIRED ENHANCED FASTENER SPACINGS FOR THE FLAT ROOF | | PERIMETER AND CORNER AREAS, OR SUBMIT THE NOA FOR THE | | CERTAINTEED FLAT ROOF WITH THE SYSTEM, EXPOSURE | | CATEGORY, ROOF HEIGHT, AND ENHANCED NAILING PATTERNS | | CIRCLED OR HIGHLIGHTED ON THE DOCUMENT. | | | | CHRISTOPHER L. COLE | | BUILDING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|