2017-10-12 16:14:58 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| PLAN PROVIDED STATES THIS THIS CATEGORY OF SUNROOM IS |
| EXEMPT FROM RECEPTACLE REQUIREMENTS PER AAMA/NPEA/NSA |
| 2100-02. HOWEVER, THERE IS NO EXEMPTION IN THE FLORIDA |
| BUILDING CODE RESIDENTIAL OR THE NATIONAL ELECTRICAL |
| CODE THAT RECOGNIZES THE ABOVE STATEMENT. THE FBC |
| RESIDENTIAL STATES: "E3901.2 GENERAL PURPOSE RECEPTACLE |
| DISTRIBUTION. IN EVERY KITCHEN, FAMILY ROOM, DINING |
| ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN, SUN ROOM, |
| BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR AREA OF |
| DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN |
| SECTIONS E3901.2.1 THROUGH E3901.2.3 (SEE FIGURE |
| E3901.2)." |
| |
| PROVIDE RESPONSES TO THE BELOW PREVIOUS COMMENTS. |
| |
| PREVIOUS ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE OUTLETS PER THE SPACING REQUIREMENTS OF NEC |
| AND FBC. NEC 210.52(A), FBC RE3901.2 |
| 2. PROVIDE AFCI PROTECTION FOR LIGHTING AND POWER |
| OUTLETS INSTALLED. ALL 120-VOLT, SINGLE PHASE, 15 AND |
| 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING |
| UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL |
| HAVE AFCI PROTECTION. NEC 210.12, FBC RE3902.12 |
| 3. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED |
| CIRCUITS, INDICATE WIRE AND BREAKER SIZE. NEC 215.5, |
| 408.4, FBC 107.2.1 |
| 4. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND |
| VALUE OF WORK. FBC 105.1, 109.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |