2017-06-02 13:49:11CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE OUTLETS PER THE SPACING REQUIREMENTS OF NEC
 AND FBC. NEC 210.52(A), FBC RE3901.2
 2. PROVIDE AFCI PROTECTION FOR LIGHTING AND POWER
 OUTLETS INSTALLED. ALL 120-VOLT, SINGLE PHASE, 15 AND
 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN DWELLING
 UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL
 HAVE AFCI PROTECTION. NEC 210.12, FBC RE3902.12
 3. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED
 CIRCUITS, INDICATE WIRE AND BREAKER SIZE. NEC 215.5,
 408.4, FBC 107.2.1
 4. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE AND
 VALUE OF WORK. FBC 105.1, 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  