2017-06-02 13:09:21 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| ELECTRICAL REVIEW COMMENTS: |
| |
| 1. PROVIDE FLOOR PLAN SHOWING SMOKE ALARMS. IF NONE ARE |
| EXISTING, OR NOT TO CODE, SHOW AS NEW INSTALLATION. FBC |
| 107.2.1, FBC R314, R315 |
| 2. PROVIDE CORRECTION SHOWING AFCI PROTECTION. ALL |
| 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| PROTECTION. NEC 210.12, FBC RE3902.12 |
| 3. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED |
| CIRCUITS, INDICATE WIRE AND BREAKER SIZE. NEC 408.4, |
| 215.5, FBC 107.2, 107.3.5 |
| 4. PROVIDE CORRECTION FOR MISSING GFCI OUTLET ON REAR |
| OF HOUSE. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. NEC |
| 210.52(E)(1) FBC RE3901.7 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |