2017-06-07 10:54:04RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 PERMIT APPLICATION NEEDS THE NOTARIZED SIGNATURE OF THE
 OWNER AND THE CONTRACTOR. ALSO, NOTICE OF COMMENCEMENT
 WILL BE REQUIRED.
  
 1- DESCRIPTION OF THE SCOPE OF WORK SHOWN ON THE PERMIT
 APPLICATION IS INCORRECT. THIS IS NOT A "RENOVATION
 BACK PATIO". ACCORDING TO PLANS SUBMITTED AND PREVIOUS
 EXPIRED PERMITS FROM THE SAME CONTRACTOR (14110641 AND
 15100254), THIS IS AN ADDITION AT THE REAR OF THE HOUSE
 NOT A "RENOVATION BACK PATIO" AS SPECIFIED ON THE
 PERMIT APPLICATION. . CONTRACTOR TO REVISE DESCRIPTION
 OF WORK ON THE PERMIT APPLICATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- THE $2,000 VALUATION DECLARED IN THE PERMIT
 APPLICATION IS EXTREMELY LOW. VALUATION TO INCLUDE ALL
 THE LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT
 AND ALL DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED TO $30,000
 +/-. THE PERMIT FEE BALANCE IS $813.56. NOTE: NEED TO
 PAY AT LEAST $163.56 TO COVER THE PLAN REVIEW FEES. THE
 BALANCE CAN BE PAID OFF AT TIME OF PERMIT ISSUANCE.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 4- THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT
 EXPOSURE "C". REVISE CODE INFORMATION SPECIFICATIONS
 SHOWN ON SHEET 1 AS REQUIRED. SEC. R301.2.1.4
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- LETTERING IN THE DESIGN LOADS INFORMATION ON CODE
 INFORMATION SHOWN ON SHEET 1 IS TOO SMALL AND IS NOT
 LEGIBLE. PROVIDE LARGER AND CLEAR LETTERING. SEC.
 107.2.1.4 CITY AMENDMENTS.
  
 6- LETTERING ON THE FRAMING DETAIL ON THE TOP RIGHT OF
 SHEET 1 IS TOO SMALL AND IS NOT LEGIBLE. PROVIDE LARGER
 AND CLEAR LETTERING. SEC. 107.2.1.4 CITY AMENDMENTS.
 NOTE: ALSO, CHECK SIZE OF STUDS TO MATCH SIZE SPECIFIED
 ON THE WALL SECTION DETAIL ON SAME DRAWING.
  
 7- PROVIDE COMPLETE SPECIFICATIONS FOR THE STEEL STRAPS
 SHOWN ON THE FRAMING DETAIL ON THE TOP HAND RIGHT SIDE
 OF SHEET 1. SPECIFY MANUFACTURER SPECIFIC STRAP AND
 SIZE. NEED TO SPECIFY STRAP IN ORDER TO GET THE
 REQUIRED PRODUCT APPROVAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 8- SPACING OF THE BOTTOM SILL ANCHORS SPECIFIED ON THE
 WALL SECTION DETAIL DOESN'T MATCH SPACING SHOWN ON THE
 FRAMING DETAIL ON TOP RIGHT SIDE OF SHEET 1. REVISE AS
 REQUIRED TO MATCH.
  
 9- EAST ELEVATION DOESN'T MATCH FLOOR PLAN. MISSING THE
 WINDOW. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 10- SIZE OF SIMPSON STRAPS SHOWN ON THE WALL SECTION
 DON'T MATCH SIZE OF STRAPS SHOWN ON THE ROOF PLAN.
 REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 11- REVISE ENERGY CALCULATIONS FORM R402-2014
 SUBMITTED:
 A) OWNER OR LEGALLY DESIGNATED AGENT NEEDS TO CERTIFY
 AT THE BOTTOM OF THE FORM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 IT LOOKS LIKE THE ENERGY CALCULATIONS WERE CERTIFIED BY
 THE SAME PERSON WHO PREPARED THE CALCULATIONS. PROVIDE
 PROOF THAT THIS PERSON IS THE LEGALLY DESIGNATED AGENT
 FOR THE OWNER OR HAVE THE OWNER CERTIFY THE
 CALCULATIONS AT THE BOTTOM OF FORM.
  
 B) PROVIDE THE OWNER'S NAME ON TOP OF FORM. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION,
  
 C) REVISE ITEM #1. THIS IS AN ADDITION NO EXISTING
 CONSTRUCTION. IT WAS NEVER PERMITTED SO IT NEEDS TO
 COMPLY WITH CURRENT CODE FOR NEW CONSTRUCTION. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION,
  
 D) THE WINDOWS INFORMATION ON ITEM #6 DOESN'T MATCH
 INFORMATION SHOWN ON TABLE R402A ON SECOND PAGE
 SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION,
  
 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) EXTERIOR SWING DOOR: INFORMATION SUBMITTED DOESN'T
 HAVE THE DRAWINGS FOR THE EXTERIOR DOOR. PROVIDE
 COMPLETE PRODUCT APPROVAL INFORMATION INCLUDING THE
 DOOR DRAWINGS AND NEED TO PROVIDE THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS
 SUBMITTED.
  
 B) FLAT ROOF ASSEMBLY. NOTE: MIAMI-DADE NOA 14-1028.02
 SUBMITTED IS NOT FOR A FLAT ROOF ASSEMBLY. NOA
 SUBMITTED IS AN UNDERLAYMENT FOR SHINGLES OR ROOF TILE.
 NEED TO PROVIDE PRODUCT APPROVAL FOR FLAT ROOF
 ASSEMBLIES. IN ADDITION, NEED TO CLEARLY SPECIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED. AND, NEED
 TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES. NEED RAS 117 CALCULATIONS TO MEET
 THE DESIGN PRESSURES REQUIRED BY SEC. R301.1
 FBC-RESIDENTIAL.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS ON SHEET 1. NOTE: PROVIDE THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR ARCHITECT TO LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO EACH SPECIFIED CONNECTOR.
  
 13- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 14- ARCHITECT OF RECORD TO SPECIFY WINDOW MULLION SIZE
 TO VERIFY COMPLIANCE WITH THE CALCULATED DESIGN
 PRESSURES AND PRODUCT APPROVAL FL18427 SUBMITTED. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE SUBMIT OLD DRAWINGS FOR REFERENCE WHEN NEW
 REVISED DRAWINGS ADDRESSING THE COMMENTS ARE SUBMITTED.
  