Plan Review Notes
Plan Review Notes For Permit 17050622
Permit Number 17050622
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-18 16:14:441ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17050622
 5/18/17
  
 1) SHEET M6.1 LISTED IN THE INDEX WAS NOT INCLUDED IN
 THE PLAN SETS- PLEASE PROVIDE THE PLAN.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE THE FLEX DUCT SIZES AND AN AIR DEVICE
 SCHEDULE
  
 4) M2.1: RELOCATE THE FIRE DAMPER SHOWN IN THE O/A DUCT
 RUN IN THE MIDDLE OF THE ROOM TO THE DUCT PENETRATION
 AT THE NEW FIRE-RATED WALL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER